GE Multilin
G30 Generator Protection System
E-3
APPENDIX E
E.1 IEC 60870-5-104
E
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the set
<30> to <40> are used.
Process information in control direction
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
System information in monitor direction
System information in control direction
<21> := Measured value, normalized value without quantity descriptor
M_ME_ND_1
<30> := Single-point information with time tag CP56Time2a
M_SP_TB_1
<31> := Double-point information with time tag CP56Time2a
M_DP_TB_1
<32> := Step position information with time tag CP56Time2a
M_ST_TB_1
<33> := Bitstring of 32 bits with time tag CP56Time2a
M_BO_TB_1
<34> := Measured value, normalized value with time tag CP56Time2a
M_ME_TD_1
<35> := Measured value, scaled value with time tag CP56Time2a
M_ME_TE_1
<36> := Measured value, short floating point value with time tag CP56Time2a
M_ME_TF_1
<37> := Integrated totals with time tag CP56Time2a
M_IT_TB_1
<38> := Event of protection equipment with time tag CP56Time2a
M_EP_TD_1
<39> := Packed start events of protection equipment with time tag CP56Time2a
M_EP_TE_1
<40> := Packed output circuit information of protection equipment with time tag CP56Time2a
M_EP_TF_1
<45> := Single command
C_SC_NA_1
<46> := Double command
C_DC_NA_1
<47> := Regulating step command
C_RC_NA_1
<48> := Set point command, normalized value
C_SE_NA_1
<49> := Set point command, scaled value
C_SE_NB_1
<50> := Set point command, short floating point value
C_SE_NC_1
<51> := Bitstring of 32 bits
C_BO_NA_1
<58> := Single command with time tag CP56Time2a
C_SC_TA_1
<59> := Double command with time tag CP56Time2a
C_DC_TA_1
<60> := Regulating step command with time tag CP56Time2a
C_RC_TA_1
<61> := Set point command, normalized value with time tag CP56Time2a
C_SE_TA_1
<62> := Set point command, scaled value with time tag CP56Time2a
C_SE_TB_1
<63> := Set point command, short floating point value with time tag CP56Time2a
C_SE_TC_1
<64> := Bitstring of 32 bits with time tag CP56Time2a
C_BO_TA_1
<70> := End of initialization
M_EI_NA_1
<100> := Interrogation command
C_IC_NA_1
<101> := Counter interrogation command
C_CI_NA_1
<102> := Read command
C_RD_NA_1
<103> := Clock synchronization command (see Clause 7.6 in standard)
C_CS_NA_1
<104> := Test command
C_TS_NA_1
<105> := Reset process command
C_RP_NA_1
<106> := Delay acquisition command
C_CD_NA_1
<107> := Test command with time tag CP56Time2a
C_TS_TA_1
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...