G30 Generator Protection System
B-41
APPENDIX B
B.4 MEMORY MAPPING
B
Third Harmonic Neutral Undervoltage (Read/Write Grouped Setting)
66DA
Third Harmonic Neutral Undervoltage Function
0 to 1
---
1
F102
0 (Disabled)
66DB
Third Harmonic Neutral Undervoltage Pickup
0 to 3
pu
0.0001
F003
3000
66DD
Third Harmonic Neutral Undervoltage Delay
0 to 600
s
0.01
F001
0
66DE
Third Harmonic Neutral Undervoltage Max Power
0 to 1.25
pu
0.001
F003
200
66E0
Third Harmonic Neutral Undervoltage Min Power
0 to 1.25
pu
0.001
F003
200
66E2
Third Harmonic Neutral Undervoltage Volt Supervision
0 to 1.25
pu
0.001
F001
500
66E3
Third Harmonic Neutral Undervoltage Block
0 to 4294967295
---
1
F300
0
66E5
Third Harmonic Neutral Undervoltage Target
0 to 2
---
1
F109
0 (Self-reset)
66E6
Third Harmonic Neutral Undervoltage Events
0 to 1
---
1
F102
0 (Disabled)
66E7
Reserved (4 items)
0 to 65535
---
1
F001
0
Generator Unbalance (Read/Write Grouped Setting)
66F0
Generator Unbalance Function
0 to 1
---
1
F102
0 (Disabled)
66F1
Generator Unbalance Source
0 to 5
---
1
F167
0 (SRC 1)
66F2
Generator Unbalance Inom
0 to 1.25
pu
0.001
F001
800
66F3
Generator Unbalance Stage 1 Pickup
0 to 100
%
0.01
F001
800
66F4
Generator Unbalance Stage 1 K value
0 to 100
---
0.01
F001
100
66F5
Generator Unbalance Stage 1 Tmin
0 to 50
s
0.001
F001
250
66F6
Generator Unbalance Stage 1 Tmax
0 to 1000
s
0.1
F001
6000
66F7
Generator Unbalance Stage 1 K Reset
0 to 1000
s
0.1
F001
2400
66F8
Generator Unbalance Stage 2 Pickup
0 to 100
%
0.01
F001
300
66F9
Generator Unbalance Stage 2 Pickup Delay
0 to 1000
s
0.1
F001
50
66FA
Generator Unbalance Block
0 to 4294967295
---
1
F300
0
66FC
Generator Unbalance Target
0 to 2
---
1
F109
0 (Self-reset)
66FD
Generator Unbalance Events
0 to 1
---
1
F102
0 (Disabled)
66FE
Reserved (3 items)
0 to 65535
---
1
F001
0
Stator Ground Source (Read/Write Grouped Setting)
670A
Stator Ground Source
0 to 5
---
1
F167
0 (SRC 1)
Stator Ground (Read/Write Grouped Setting
6720
Stator Ground Function
0 to 1
---
1
F102
0 (Disabled)
6721
Stator Ground Stage 1 Pickup
0 to 0.9
pu
0.001
F001
150
6722
Stator Ground Stage 1 Pickup Delay
0 to 600
s
0.01
F001
100
6723
Stator Ground Stage 1 Supv
0.001 to 0.1
pu
0.0001
F001
57
6724
Stator Ground Stage 2 Pickup
0 to 0.9
pu
0.001
F001
150
6725
Stator Ground Stage 2 Pickup Delay
0 to 600
s
0.01
F001
0
6726
Stator Ground Stage 2 Supv
0.001 to 0.1
pu
0.0001
F001
45
6727
Stator Ground Block
0 to 4294967295
---
---
F300
0
6729
Stator Ground Target
0 to 2
---
1
F109
0 (Self-reset)
672A
Stator Ground Event
0 to 1
---
1
F102
0 (Disabled)
672B
Reserved (5 items)
0 to 65535
---
1
F001
0
Split Phase Protection (Read/Write Grouped Setting)
6730
Split Phase Protection Function
0 to 1
---
1
F102
0 (Disabled)
6731
Split Phase Protection Source
0 to 5
---
1
F167
0 (SRC1)
6732
Split Phase Protection Load Source
0 to 5
---
1
F167
0 (SRC1)
6733
Split Phase Protection Phase A Pickup
0.02 to 1.500
pu
0.001
F001
200
6734
Split Phase Protection Phase A Offset
0 to 1
pu
0.001
F001
0
6735
Split Phase Protection Phase A Slope
0 to 100
%
0.1
F001
0
6736
Split Phase Protection Phase B Pickup
0.02 to 1.5
pu
0.001
F001
200
6737
Split Phase Protection Phase B Offset
0 to 1
pu
0.001
F001
0
6738
Split Phase Protection Phase B Slope
0 to 100
%
0.1
F001
0
6739
Split Phase Protection Phase C Pickup
0.02 to 1.5
pu
0.001
F001
200
673A
Split Phase Protection Phase C Offset
0 to 1
pu
0.001
F001
0
673B
Split Phase Protection Phase C Slope
0 to 100
%
0.1
F001
0
673C
Split Phase Protection Minimum Load
0 to 1
pu
0.01
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 33 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...