GE Multilin
G30 Generator Protection System
F-1
APPENDIX F
F.1 DEVICE PROFILE DOCUMENT
F
APPENDIX F DNP COMMUNICATIONSF.1DEVICE PROFILE DOCUMENT
F.1.1 DNP V3.00 DEVICE PROFILE
The following table provides a ‘Device Profile Document’ in the standard format defined in the DNP 3.0 Subset Definitions
Document.
Table F–1: DNP V3.00 DEVICE PROFILE (Sheet 1 of 3)
(Also see the IMPLEMENTATION TABLE in the following section)
Vendor Name:
General Electric Multilin
Device Name:
UR Series Relay
Highest DNP Level Supported:
For Requests:
Level 2
For Responses:
Level 2
Device Function:
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Control Relay Output Block (Object 12)
Binary Counters (Object 20)
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
File Transfer (Object 70)
Internal Indications (Object 80)
Maximum Data Link Frame Size (octets):
Transmitted:
292
Received:
292
Maximum Application Fragment Size (octets):
Transmitted:
configurable up to 2048
Received:
2048
Maximum Data Link Re-tries:
None
Fixed at 3
Configurable
Maximum Application Layer Re-tries:
None
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...