B-28
G30 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
3FDC
...Repeated for Field Unit 5
3FE5
...Repeated for Field Unit 6
3FEE
...Repeated for Field Unit 7
3FF7
...Repeated for Field Unit 8
Passwords (Read/Write Command)
4000
Command Password Setting
0 to 4294967295
---
1
F202
(none)
Passwords (Read/Write Setting)
400A
Setting Password Setting
0 to 4294967295
---
1
F202
(none)
Passwords (Read/Write)
4014
Command Password Entry
0 to 4294967295
---
1
F202
(none)
401E
Setting Password Entry
0 to 4294967295
---
1
F202
(none)
Passwords (Read Only)
4028
Command Password Status
0 to 1
---
1
F102
0 (Disabled)
4029
Setting Password Status
0 to 1
---
1
F102
0 (Disabled)
Passwords (Read/Write Setting)
402A
Command Password Access Timeout
5 to 480
min
1
F001
5
402B
Setting Password Access Timeout
5 to 480
min
1
F001
30
402C
Invalid Password Attempts (before lockout)
2 to 5
---
1
F001
3
402D
Password Lockout Duration
5 to 60
min
1
F001
5
Passwords (Read/Write)
402E
Password Access Events
0 to 1
---
1
F102
0 (Disabled)
Passwords (Read/Write Setting)
402F
Local Setting Auth
1 to 4294967295
---
1
F300
1
4031
Remote Setting Auth
0 to 4294967295
---
1
F300
1
4033
Access Auth Timeout
5 to 480
min
1
F001
30
User Display Invoke (Read/Write Setting)
4040
Invoke and Scroll Through User Display Menu Operand
0 to 4294967295
---
1
F300
0
LED Test (Read/Write Setting)
4048
LED Test Function
0 to 1
---
1
F102
0 (Disabled)
4049
LED Test Control
0 to 4294967295
---
1
F300
0
Preferences (Read/Write Setting)
404F
Language
0 to 5
---
1
F531
0 (English)
4050
Flash Message Time
0.5 to 10
s
0.1
F001
10
4051
Default Message Timeout
10 to 900
s
1
F001
300
4052
Default Message Intensity
0 to 3
---
1
F101
0 (25%)
4053
Screen Saver Feature
0 to 1
---
1
F102
0 (Disabled)
4054
Screen Saver Wait Time
1 to 65535
min
1
F001
30
4055
Current Cutoff Level
0.002 to 0.02
pu
0.001
F001
20
4056
Voltage Cutoff Level
0.1 to 1
V
0.1
F001
10
Communications (Read/Write Setting)
407D
COM2 Selection
0 to 3
---
1
F601
0 (RS485)
407E
COM1 Minimum Response Time
0 to 1000
ms
10
F001
0
407F
COM2 Minimum Response Time
0 to 1000
ms
10
F001
0
4080
Modbus Slave Address
1 to 254
---
1
F001
254
4083
RS485 Com1 Baud Rate
0 to 11
---
1
F112
8 (115200)
4084
RS485 Com1 Parity
0 to 2
---
1
F113
0 (None)
4085
RS485 Com2 Baud Rate
0 to 11
---
1
F112
8 (115200)
4086
RS485 Com2 Parity
0 to 2
---
1
F113
2 (Even)
4087
Port 1 IP Address
0 to 4294967295
---
1
F003
2130706433
4089
Port 1 IP Subnet Mask
0 to 4294967295
---
1
F003
4278190080
408B
Port 1 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
408D
Network Address NSAP
---
---
---
F074
0
4097
Port 1 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
4098
Port 2 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 20 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...