5-32
G30 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
UR relays implement only the DANP functionality. The RedBox functionality is not implemented.
The original standard IEC 62439-3 (2010) was amended to align PRP with the High-availability Seamless Redundancy
(HSR) protocol. To achieve this, the original PRP was modified at the cost of losing compatibility with the PRP 2010 ver-
sion. The revised standard IEC 62439-3 (2012) is commonly referred to as PRP-1, while the original standard is PRP-0.
The UR relays support only PRP-1.
The relay implements PRP on two of its Ethernet ports, specifically Port 2 and 3 of the CPU module. Use the previous sec-
tion (network port configuration) to configure PRP.
PRP is purchased as a separate option. If purchased (valid order code), PRP can be enabled in configuration through a
setting available on the network configuration menu, REDUNDANCY, which already has the capability of enabling failover
redundancy. The options on this setting must be changed to accommodate two types of redundancy: failover and PRP.
When REDUNDANCY is set to either failover or PRP, the ports dedicated for PRP (Port 2 and 3) operate in redundant
mode. In this mode, Port 3 uses the Mac, IP address, and mask of Port 2.
g) ROUTING
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
ROUTING 1(6)
A default route and a maximum number of six static routes can be configured.
The default route is used as the last choice when no other route towards a given destination is found.
Configure the network IP and subnet settings before configuring the routing settings.
ADDING AND DELETING STATIC ROUTES
Host routes are not supported at present.
The routing table configuration is available on the serial port and front panel. This is a deliberate decision, to avoid loss of
connectivity when remotely configuring the UR.
By default the value of the destination field is 127.0.0.1 for all static routes (1 to 6). This is equivalent to saying that the
static routes are not configured. When the destination address is 127.0.0.1, the mask and gateway must be also kept on
default values.
By default, the value of the route gateway address is 127.0.0.1. This means the default route is not configured.
To add a route:
IPV4 ROUTING
TABLE
IPV4 DEFAULT ROUTE
MESSAGE
IPV4 STATIC
NETWORK ROUTE 1
↓
MESSAGE
IPV4 STATIC
NETWORK ROUTE 6
IPV4 DEFAULT ROUTE
GATEWAY ADDRESS
127.0.0.1
Range: Standard IPV4 unicast address format
IPV4 STATIC
NETWORK ROUTE 1
RT1 DESTINATION:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
RT1 NET MASK:
255.0.0.0
Range: Standard IPV4 subnet mask format
MESSAGE
RT1 GATEWAY:
127.0.0.1
Range: Standard IPV4 unicast address format
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...