GE Multilin
G30 Generator Protection System
5-91
5 SETTINGS
5.2 PRODUCT SETUP
5
The G.703 modules are fixed at 64 kbps. The
DIRECT I/O DATA RATE
setting is not applicable to these modules.
The
DIRECT I/O CHANNEL CROSSOVER
setting applies to G30s with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. See the
Inputs
and Outputs
section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.
Table 5–12: DIRECT INPUT AND OUTPUT DATA RATES
MODULE
CHANNEL
SUPPORTED DATA RATES
74
Channel 1
64 kbps
Channel 2
64 kbps
7L
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7M
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7P
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7T
Channel 1
64 kbps, 128 kbps
7W
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
7V
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
2A
Channel 1
64 kbps
2B
Channel 1
64 kbps
Channel 2
64 kbps
2G
Channel 1
128 kbps
2H
Channel 1
128 kbps
2I
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
2J
Channel 1
64 kbps, 128 kbps
Channel 2
64 kbps, 128 kbps
76
Channel 1
64 kbps
77
Channel 1
64 kbps
Channel 2
64 kbps
75
Channel 1
64 kbps
Channel 2
64 kbps
7E
Channel 1
64 kbps
Channel 2
64 kbps
7F
Channel 1
64 kbps
Channel 2
64 kbps
7G
Channel 1
64 kbps
Channel 2
64 kbps
7Q
Channel 1
64 kbps
Channel 2
64 kbps
7R
Channel 1
64 kbps
7S
Channel 1
64 kbps
Channel 2
64 kbps
NOTE
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...