B-48
G30 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
FlexElement (Read/Write Setting) (16 modules)
9000
FlexElement 1 Function
0 to 1
---
1
F102
0 (Disabled)
9001
FlexElement 1 Name
---
---
---
F206
“FxE 1”
9004
FlexElement 1 InputP
0 to 65535
---
1
F600
0
9005
FlexElement 1 InputM
0 to 65535
---
1
F600
0
9006
FlexElement 1 Compare
0 to 1
---
1
F516
0 (LEVEL)
9007
FlexElement 1 Input
0 to 1
---
1
F515
0 (SIGNED)
9008
FlexElement 1 Direction
0 to 1
---
1
F517
0 (OVER)
9009
FlexElement 1 Hysteresis
0.1 to 50
%
0.1
F001
30
900A
FlexElement 1 Pickup
-90 to 90
pu
0.001
F004
1000
900C
FlexElement 1 DeltaT Units
0 to 2
---
1
F518
0 (Milliseconds)
900D
FlexElement 1 DeltaT
20 to 86400
---
1
F003
20
900F
FlexElement 1 Pickup Delay
0 to 65.535
s
0.001
F001
0
9010
FlexElement 1 Reset Delay
0 to 65.535
s
0.001
F001
0
9011
FlexElement 1 Block
0 to 4294967295
---
1
F300
0
9013
FlexElement 1 Target
0 to 2
---
1
F109
0 (Self-reset)
9014
FlexElement 1 Events
0 to 1
---
1
F102
0 (Disabled)
9015
...Repeated for FlexElement 2
902A
...Repeated for FlexElement 3
903F
...Repeated for FlexElement 4
9054
...Repeated for FlexElement 5
9069
...Repeated for FlexElement 6
907E
...Repeated for FlexElement 7
9093
...Repeated for FlexElement 8
90A8
...Repeated for FlexElement 9
90BD
...Repeated for FlexElement 10
90D2
...Repeated for FlexElement 11
90E7
...Repeated for FlexElement 12
90FC
...Repeated for FlexElement 13
9111
...Repeated for FlexElement 14
9126
...Repeated for FlexElement 15
913B
...Repeated for FlexElement 16
DCmA Outputs (Read/Write Setting) (24 modules)
9360
DCmA Output 1 Source
0 to 65535
---
1
F600
0
9361
DCmA Output 1 Range
0 to 2
---
1
F522
0 (–1 to 1 mA)
9362
DCmA Output 1 Minimum
–90 to 90
pu
0.001
F004
0
9364
DCmA Output 1 Maximum
–90 to 90
pu
0.001
F004
1000
9366
...Repeated for DCmA Output 2
936C
...Repeated for DCmA Output 3
9372
...Repeated for DCmA Output 4
9378
...Repeated for DCmA Output 5
937E
...Repeated for DCmA Output 6
9384
...Repeated for DCmA Output 7
938A
...Repeated for DCmA Output 8
9390
...Repeated for DCmA Output 9
9396
...Repeated for DCmA Output 10
939C
...Repeated for DCmA Output 11
93A2
...Repeated for DCmA Output 12
93A8
...Repeated for DCmA Output 13
93AE
...Repeated for DCmA Output 14
93B4
...Repeated for DCmA Output 15
93BA
...Repeated for DCmA Output 16
93C0
...Repeated for DCmA Output 17
93C6
...Repeated for DCmA Output 18
Table B–10: MODBUS MEMORY MAP (Sheet 40 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...