CHAPTER 3: INSTALLATION
PANEL CUTOUTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
3-3
3
Figure 3-2: Horizontal mounting (enhanced panel)
Figure 3-3: Horizontal mounting and dimensions (standard panel)
3.2.2 Vertical units
The L60 is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified
as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable
pushbuttons and LED indicators.
The modular design allows the relay to be upgraded and repaired by qualified service personnel. The faceplate is hinged to
allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear depth.
The case dimensions are shown in the following figure, along with panel cutout details for panel mounting. When planning
the location of your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or
from adjacent equipment.
18.370”
[466,60 mm]
842808A1.CDR
0.280”
[7,11 mm]
Typ. x 4
4.000”
[101,60 mm]
17.750”
[450,85 mm]
CUT-OUT
19.00”
(482.6 mm)
7.00”
(177.8 mm)
Horizontal front view
Horizontal top view (19”, 4 RU)
17.52”
(445.0 mm)
Brackets
repositioned for
switchgear
mounting
10.90”
(276.8 mm)
9.80”
(248.9 mm)
8.97”
(227.8 mm)
17.75”
(450.8 mm)
7.13”
(181.1 mm)
Cutout
18.37”
(466.6 mm)
4.00”
(101.6 mm)
1.57”
(39.8 mm)
4 × 0.28”
(7.1 mm)
diameter
17.72”
(450.1 mm)
14.52”
(368.8 mm)
9.52”
(241.8 mm)
8 × 0.156
Ø
5.00”
(127.0 mm)
0.375”
(9.5 mm)
0.375”
(9.5 mm)
Remote mounting, view from the rear of the panel
Bezel
outline
0.375” (9.5)
1.875”
(47.6)
0.375” (9.5)
4.875”
(121.5 mm)
6.96”
(176.8 mm)
827704B4.CDR
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...