![GE Digital Energy L60 Скачать руководство пользователя страница 310](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854310.webp)
5-180
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-85: Memory voltage logic
5.6.5.2 Phase distance (ANSI 21P, IEC PDIS)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
PHASE DISTANCE Z1(Z3)
PHASE DISTANCE Z1
PHS DIST Z1
FUNCTION: Disabled
Range: Disabled, Enabled
PHS DIST Z1 DIR:
Forward
Range: Forward, Reverse, Non-directional
PHS DIST Z1
SHAPE: Mho
Range: Mho, Quad
PHS DIST Z1 XFMR VOL
CONNECTION: None
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
PHS DIST Z1 XFMR CUR
CONNECTION: None
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
PHS DIST Z1
REACH: 2.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
PHS DIST Z1
RCA: 85°
Range: 30 to 90° in steps of 1
PHS DIST Z1 REV
REACH: 2.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
PHS DIST Z1 REV
REACH RCA: 85°
Range: 30 to 90° in steps of 1
PHS DIST Z1
COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
PHS DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
PHS DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
PHS DIST Z1 QUAD
RGT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
PHS DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
PHS DIST Z1 QUAD
LFT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
PHS DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
827842A9.CDR
Use V_1
Use V_1 memory
AND
AND
OR
AND
AND
S Q
R
RUN
Update memory
SETTING
Off = 0
Force Memory Polarization
| V_1 | < 1.15 pu
| Vrms – | V | | < Vrms / 8
| Vrms – | V | | < Vrms / 8
| Vrms – | V | | < Vrms / 8
| V_1 | > 0.80 pu
| IA | < 0.05 pu
| IB | < 0.05 pu
SETTING
Off = 0
Force Self Polarization
SETTING
= VA, Vrms_A
= VB, Vrms_B
Distance Source
= VC, Vrms_C
= V_1
= IA
= IB
= IC
| IC | < 0.05 pu
| V_1 | < 0.10 pu
TIMER
5 cycles
0
TIMER
6 cycles
0
AND
AND
OR
SETTING
Memory duration
0
T
reset
Tracking Freq, *SRCx Freq
= IC
| f
- f | > 1 Hz
TRACK
SRC
*SRCx is the source used in distance
L90 Only
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...