![GE Digital Energy L60 Скачать руководство пользователя страница 436](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854436.webp)
5-306
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
BKR ONE POLE OPEN
— This setting selects a FlexLogic operand that indicates that the breaker has opened correctly
following a single phase to ground fault and the autoreclose scheme can start timing the single pole dead time (for 1-2
reclose sequence for example, breaker 1 trips single pole and breaker 2 trips 3 pole).
The scheme has a pre-wired input that indicates breaker status.
BKR 3 POLE OPEN
— This setting selects a FlexLogic operand that indicates that the breaker has opened three pole and the
autoreclose scheme can start timing the three pole dead time. The scheme has a pre-wired input that indicates breaker
status.
AR 3-P DEAD TIME 1
— This is the dead time following the first three pole trip. This intentional delay can be used for a high-
speed three-pole autoreclose. Set it longer than the estimated de-ionizing time following the three-pole trip.
AR 3-P DEAD TIME 2
— This is the dead time following the second three-pole trip or initiated by the
AR 3P TD INIT
input. This
intentional delay is typically used for a time delayed three-pole autoreclose (as opposed to high speed three-pole
autoreclose).
AR 3-P DEAD TIME 3
— This setting represents the dead time following the third three-pole trip.
AR 3-P DEAD TIME 4
— This setting represents the dead time following the fourth three-pole trip.
AR EXTEND DEAD T 1
— This setting selects an operand that adapts the duration of the dead time for the first shot to the
possibility of non-simultaneous tripping at the two line ends. Typically this is the operand set when the communication
channel is out of service.
AR DEAD TIME 1 EXTENSION
— This timer sets the length of the dead time 1 extension for possible non-simultaneous tripping
of the two ends of the line.
AR RESET
— This setting selects the operand that forces the autoreclose scheme from any state to reset. Typically this is a
manual reset from lockout, local, or remote.
AR RESET TIME
— A reset timer output resets the recloser following a successful reclosure sequence. The setting is based on
the breaker time that is the minimum time required between successive reclose sequences.
AR BKR CLOSED
— This setting selects an operand that indicates that the breakers are closed at the end of the reset time
and the scheme can reset.
AR BLOCK
— This setting selects the operand that blocks the autoreclose scheme (it can be a sum of conditions, such as
time delayed tripping, breaker failure, and bus differential protection. If the block signal is present before autoreclose
scheme initiation, the
AR DISABLED
FlexLogic operand is set. If the block signal occurs when the scheme is in the RIP state,
the scheme is sent to lockout.
AR PAUSE
— The pause input offers the ability to freeze the autoreclose cycle until the pause signal disappears. This can be
done when a trip occurs and simultaneously or previously, some conditions are detected, such as out-of step or loss of
guard frequency, or a remote transfer trip signal is received. When the pause signal disappears the autoreclose cycle is
resumed. This feature can also be used when a transformer is tapped from the protected line and a reclose is not desirable
until it is disconnected from the line. In this situation, the reclose scheme pauses until the transformer is disconnected.
AR INCOMPLETE SEQ TIME
— This timer is used to set the maximum time interval allowed for a single reclose shot. It is
started whenever a reclosure is initiated and is active until the CLOSE BKR1 or CLOSE BKR2 signal is sent. If all conditions
allowing a breaker closure are not satisfied when this time expires, the scheme goes to “Lockout”. The minimum
permissible setting is established by the
AR 3-P DEAD TIME 2
timer setting. Settings beyond this determine the wait time for
the breaker to open so that the reclose cycle can continue and/or for the AR PAUSE signal to reset and allow the reclose
cycle to continue and/or for the AR BKR1 BLK signal to disappear and allow the AR CLOSE BKR1 signal to be sent.
AR BLOCK BKR2
— This input selects an operand that blocks the reclose command for breaker 2. This condition can be for
example: breaker low air pressure, reclose in progress on another line (for the central breaker in a breaker and a half
arrangement), or a sum of conditions combined in FlexLogic.
AR CLOSE TIME BKR2
— This setting represents the closing time for the breaker 2 from the moment the "Close" command is
sent to the moment the contacts are closed.
AR TRANSFER 1 TO 2
— This setting establishes how the scheme performs when the breaker closing sequence is 1-2 and
breaker 1 is blocked. When set to “Yes” the closing command is transferred direct to breaker 2 without waiting the transfer
time. When set to “No” the closing command is blocked by the AR BKR1 BLK signal and the scheme will be sent to lockout
by the incomplete sequence timer.
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...