CHAPTER 5: SETTINGS
SYSTEM SETUP
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-127
5
5.4.6.2 FlexCurve configuration with EnerVista software
The EnerVista software allows for easy configuration and management of FlexCurves and their associated data points.
Prospective FlexCurves can be configured from a selection of standard curves to provide the best approximate fit, then
specific data points can be edited afterwards. Alternately, curve data can be imported from a specified file (.csv format) by
selecting the EnerVista
Import Data From
setting (
Settings > System Setup > FlexCurves > FlexCurve
).
Curves and data can be exported, viewed, and cleared by clicking the appropriate buttons. FlexCurves are customized by
editing the operating time (ms) values at pre-defined per-unit current multiples. Note that the pickup multiples start at zero
(implying the "reset time"), operating time below pickup, and operating time above pickup.
5.4.6.3 Recloser curve editing
Recloser curve selection is special in that recloser curves can be shaped into a composite curve with a minimum response
time and a fixed time above a specified pickup multiples. There are 41 recloser curve types supported. These definite
operating times are useful to coordinate operating times, typically at higher currents and where upstream and
downstream protective devices have different operating characteristics. The recloser curve configuration window shown
here appears when the
Initialize From
setting in the EnerVista software is set to “Recloser Curve” and the
Initialize
FlexCurve
button is clicked.
Figure 5-52: Recloser curve initialization
5.4.6.4 Example
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight times pickup with an operating time of 30 ms. At approximately four times pickup, the curve operating
time is equal to the MRT and from then onwards the operating time remains at 200 ms.
NOTE
The
Multiplier
and
Adder
settings only affect the curve portion of the characteristic and not the MRT and HCT
settings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio.
842721A1.CDR
Multiplier:
Scales (multiplies) the curve operating times
Addr:
Adds the time specified in this field (in ms) to each
operating time value.
curve
Minimum Response Time (MRT):
If enabled, the MRT setting
defines the shortest operating time even if the curve suggests
a shorter time at higher current multiples. A composite operating
characteristic is effectively defined. For current multiples lower
than the intersection point, the curve dictates the operating time;
otherwise, the MRT does. An information message appears
when attempting to apply an MRT shorter than the minimum
curve time.
High Current Time:
HCT Ratio
HCT
Allows the user to set a pickup multiple
from which point onwards the operating time is fixed. This is
normally only required at higher current levels. The
defines the high current pickup multiple; the
defines the
operating time.
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...