CHAPTER 5: SETTINGS
FLEXLOGIC
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-153
5
A FlexElement is a universal comparator used to monitor any analog actual value calculated by the relay or a net
difference of any two analog actual values of the same type. The effective operating signal can be treated as a signed
number or its absolute value can be used.
FlexElements run every half power cycle (every four protection passes).
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold, as
per your choice.
Figure 5-71: FlexElement logic
FLEXELEMENT 1 +IN
— This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if
this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element
does not assert its output operands.
FLEXELEMENT 1
PICKUP: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
FLEXELEMENT 1
HYSTERESIS: 3.0%
Range: 0.1 to 50.0% in steps of 0.1
FLEXELEMENT 1 dt
UNIT: Milliseconds
Range: Milliseconds, Seconds, Minutes
FLEXELEMENT 1 dt:
20
Range: 20 to 86400 in steps of 1
FLEXELEMENT 1 PKP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
FLEXELEMENT 1 RST
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
FLEXELEMENT 1 BLK:
Off
Range: FlexLogic operand
FLEXELEMENT 1
TARGET: Self-reset
Range: Self-reset, Disabled, Latched
FLEXELEMENT 1
EVENTS: Disabled
Range: Disabled, Enabled
842004A4.CDR
FLEXELEMENT 1
FUNCTION:
SETTING
Enabled = 1
SETTINGS
FLEXELEMENT 1 INPUT MODE:
FLEXELEMENT 1 COMP MODE:
FLEXELEMENT 1 DIRECTION:
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 dt UNIT:
FLEXELEMENT 1 dt:
RUN
FLEXELEMENT 1 +IN:
SETTINGS
Actual Value
FLEXLOGIC OPERANDS
FxE 1 DPO
FxE 1 OP
FxE 1 PKP
FLEXELEMENT 1 -IN:
Actual Value
+
-
FlexElement 1 OpSig
ACTUAL VALUE
FLEXELEMENT 1 BLK:
SETTING
Off = 0
AND
t
PKP
t
RST
SETTINGS
FLEXELEMENT 1 RST
DELAY:
FLEXELEMENT 1 PKP
DELAY:
FLEXELEMENT 1 INPUT
HYSTERESIS:
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...