2-14
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
SIGNAL PROCESSING
CHAPTER 2: PRODUCT DESCRIPTION
2
Figure 2-4: UR signal processing
The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems.
The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking
system.
The A/D converter has the following ranges of AC signals:
Voltages:
Eq. 2-1
Currents:
Eq. 2-2
Current harmonics are estimated based on raw samples with the use of the full-cycle Fourier filter. Harmonics 2nd through
25th are estimated.
True RMS value for the current is calculated on a per-phase basis. The true RMS can be used for demand recording or as an
input signal to Time Overcurrent function, if the latter is intended for thermal protection. The true RMS is calculated as per
the widely accepted definition:
Eq. 2-3
From
CT/VT
U
I
Analog Inputs
Analog low-
pass filter
Analog-to-
Digital
Converter
A
Digital band-
pass filter
DSP module
Phasor
estimation
½ cycle
Fourier
1 cycle
Fourier
RMS
values
Fundamen
tal freq.
Phasors,
Seq. com-
ponents
D
Sampling
frequency
CPU module
I>
Z<
U<
Protection
algorithms
IRIG-B
IEEE
1588
SNTP
Tracking
frequency
selection,
estimation
Accurate
Real-Time
clock
Synchrophasors
calculations
Serial
ports
Ethernet
ports
Communi-
cation
protocols
Control
elements,
monitoring
elements,
FlexLogic,
Aggregation,
post-filtering
Contact Inputs
module
HMI
Ddebounce
filtering
Optoisolated
Analog Inputs
module
DCmA, RTD
A
D
Inter-relay
comms
module
Channel
monitoring
CRC check
G.703, RS-422,
C37.94, direct fiber
Contact Outputs
module
Et
h
e
rn
e
t
S
eria
l
PMU (IEEE C37.118,
IEC 61850-90-5)
IEC 61850 (GOOSE,
MMS Server)
DNP, Modbus,
IEC60870
Comtrade, data
logger
Events
Inter-relay
comms
module
Frequency
T
Analog Outputs
module
Time stamping
Synchro-
phasors
filtering
859740A1.vsd
2
±
260 V
( )
⋅
2
±
46rated A
( )
⋅
I
RMS t
( )
1
T
--
i
2
t
( )
t
d
t T
–
(
)
t
=
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...