![GE Digital Energy L60 Скачать руководство пользователя страница 289](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854289.webp)
CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-159
5
The phase comparison tripping scheme menu provides the main setup for the phase comparison relay.
See the Application of Settings chapter for more information on individual settings.
87PC SCHEME SELECT
— Selects the phase comparison element scheme logic as follows:
2TL-TR-SPC-2FC — Two-terminal line, permissive tripping, single phase comparison, two frequency channel.
87PC FDH SUPV:
Off
Range: FlexLogic operand
87PC CH1 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
87PC CH2 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
87PC CH1 DELAY:
0.0 ms
Range: 0.0 to 30.0 ms in steps of 0.1
87PC CH2 DELAY:
0.0 ms
Range: 0.0 to 30.0 ms in steps of 0.1
87PC CH1 RX VOLT:
12.0 V
Range: 0.0 to 125.0 V in steps of 0.1
87PC CH2 RX VOLT:
12.0 V
Range: 0.0 to 125.0 V in steps of 0.1
87PC TRIP SECURITY:
First Coincidence
Range: First Coincidence, Enhanced
87PC SECOND COINCID
TIMER: 40 ms
Range: 10 to 200 ms in steps of 1
87PC STABILITY
ANGLE: 75°
Range: 40 to 140° in steps of 5
87PC ENHANCED STAB
ANGLE: 110°
Range: 40 to 180° in steps of 5
87PC PICKUP DELAY:
0 ms
Range: 0 to 50 ms in steps of 1
87PC STOP TX:
Off
Range: FlexLogic operand
87PC TX RESET DELAY:
0 ms
Range: 0 to 1000 ms in steps of 1
87PC RESET DELAY:
30 ms
Range: 0 to 200 ms in steps of 1
87PC TRANS BLOCK
PICKUP: 0.030 s
Range: 0 to 65.535 s in steps of 0.001
87PC TRANS BLOCK
RESET: 0.030 s
Range: 0 to 65.535 s in steps of 0.001
87PC CHNL LOSS TRIP
WINDOW: 0 msec
Range: 0 to 500 ms in steps of 1
87PC HIGH-SPEED TRIP
CONTACT 1: Off
Range: Off, available contact outputs
87PC HIGH-SPEED TRIP
CONTACT 2: Off
Range: Off, available contact outputs
87PC TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled
87PC EVENTS:
Disabled
Range: Disabled, Enabled
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...