CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-171
5
The negative-sequence overcurrent advanced fault detector element responds to the increment of the magnitude of the
negative-sequence current over a specified threshold. Thresholds are provided for low-set control of keying and high-set
operation control of tripping.
NEG SEQ I_2 FD FUNCTION
— This setting enables or disables the negative-sequence overcurrent fault detection. Note that
all fault detectors operate in parallel with the 87PC function. To effectively disable the overcurrent fault detectors under
the main 87PC menu, set their threshold very high.
NEG SEQ I_2 FDL PICKUP
— This setting specifies the pickup of the low-set stage of the element used to control the key
operation. The nominal current of the phase CT bank of the relay is 1 pu.
NEG SEQ I_2 FDH PICKUP
— This setting specifies the pickup of the high-set stage of the element used to control the trip
operation. The nominal current of the phase CT bank of the relay is 1 pu.
NEG SEQ I_2 BLK
— The fault detector is hard-wired to the 87PC scheme. It can be disabled permanently using the function
setting or blocked temporarily with this setting. This setting selects a FlexLogic operand that blocks this fault detector
when asserted.
NEG SEQ I_2 FD TARGET
— This setting controls targets of the negative-sequence overcurrent advanced fault detector
function. These targets operate independently from the 87PC targets.
NEG SEQ I_2 FD EVENTS
— This setting controls event recording of the negative-sequence overcurrent advanced fault
detector function. These events are logged independently from the 87PC events.
Figure 5-80: Negative-sequence overcurrent advanced fault detector logic
5.6.3.8 Positive-sequence overcurrent fault detection
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE COMPARISON ELEMENTS
ADVANCED FAULT
DETECTORS
POSITIVE-SEQUENCE CURRENT
The positive-sequence overcurrent advanced fault detector element responds to the increment of the magnitude of the
positive-sequence current over a specified threshold. Thresholds are provided for low-set control of keying and high-set
operation control of tripping.
POSITIVE-SEQUENCE
CURRENT
POS SEQ I_1 FD
FUNCTION: Disabled
Range: Disabled, Enabled
POS SEQ I_1 FDL
PICKUP: 0.10 pu
Range: 0.20 to 5.00 pu in steps of 0.01
POS SEQ I_1 FDH
PICKUP: 0.50 pu
Range: 0.50 to 15.00 pu in steps of 0.01
POS SEQ I_1 BLK:
Off
Range: FlexLogic operand
POS SEQ I_1 FD
TARGET: Self-reset
Range: Self-Reset, Latched, Disabled
POS SEQ I_1 FD
EVENTS: Disabled
Range: Disabled, Enabled
Hardwired to the
87PC function
To square pulse
and transmit logic
SETTINGS
Enabled = 1
NEG SEQ I_2 FD FUNCTION
Off = 0
NEG SEQ I_2 BLOCK
AND
FAST MEASUREMENTS
Negative-sequence
current I_2
F1 PHASE CT BANK
L1 PHASE CT BANK
Negative-sequence
current I_2
Σ
SETTINGS
NEG SEQ I_2 FDH PICKUP
RUN
NEG SEQ I_2 FDL PICKUP
> (FDL PICKUP) / 4
> (FDH PICKUP) / 4
> (FDL PICKUP) / 4
> (FDH PICKUP) / 4
> FDL PICKUP
> FDH PICKUP
OR
OR
AND
AND
FLEXLOGIC OPERANDS
87PC I_2 FDL OP
87PC I_2 FDH OP
831030A2.CDR
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...