CHAPTER 5: SETTINGS
FLEXLOGIC
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-143
5
ELEMENT:
Trip bus
TRIP BUS 1 PKP
TRIP BUS 1 OP
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
TRIP BUS 2 to 6
Same set of operands as shown for TRIP BUS 1
ELEMENT:
Wattmetric zero-
sequence directional
WATTMETRIC 1 PKP
WATTMETRIC 1 OP
Wattmetric directional element 1 has picked up
Wattmetric directional element 1 has operated
WATTMETRIC 2
Same set of operands as per WATTMETRIC 1
FIXED OPERANDS
Off
Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On
Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS:
Contact inputs
Cont Ip 1 On
Cont Ip 2 On
↓
Cont Ip 1 Off
Cont Ip 2 Off
↓
Cont Ip 96 On
Cont Ip 96 Off
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
↓
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
current
(from detector on
form-A output only)
Cont Op 1 IOn
Cont Op 2 IOn
↓
(does not appear unless ordered)
(does not appear unless ordered)
↓
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
Cont Op 1 VOn
Cont Op 2 VOn
↓
(does not appear unless ordered)
(does not appear unless ordered)
↓
Cont Op 1 VOff
Cont Op 2 VOff
↓
(does not appear unless ordered)
(does not appear unless ordered)
↓
INPUTS/OUTPUTS
Direct inputs
DIRECT INPUT 1 On
↓
DIRECT INPUT 32 On
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
RxGOOSE DPS
RxG DPS 1 BAD
RxG DPS 1 INTERM
RxG DPS 1 OFF
RxG DPS 1 ON
Asserted while the RxGOOSE double-point status input is in the bad state
Asserted while the RxGOOSE double-point status input is in the intermediate
state
Asserted while the RxGOOSE double-point status input is off
Asserted while the RxGOOSE double-point status input is on
RxG DPS 2 to 5
Same set of operands as per RxG DPS 1
INPUTS/OUTPUTS:
RxGOOSE Booleans
RxG Bool 1 On
RxG Bool 2 On
RxG Bool 3 On
↓
RxG Bool 32 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual inputs
Virt Ip 1 On
Virt Ip 2 On
Virt Ip 3 On
↓
Virt Ip 64 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual outputs
Virt Op 1 On
Virt Op 2 On
Virt Op 3 On
↓
Virt Op 96 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
Operand type
Operand syntax
Operand description
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...