5-150
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
Figure 5-69: FlexLogic equation for virtual output 3
6.
Repeating the process described for virtual output 3, select the FlexLogic parameters for Virtual Output 4.
–
99: The final output of the equation is virtual output 4, which is parameter “= Virt Op 4".
–
98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for
the timer are established in the timer programming section.
–
97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter “OR(3)”.
–
96: The lowest input to OR #2 is operand “Cont Ip H1c On”.
–
95: The center input to OR #2 is operand “TIMER 1".
–
94: The input to timer 1 is operand “Virt Op 3 On".
–
93: The upper input to OR #2 is operand “LATCH (S,R)”.
–
92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR,
which is parameter “OR(4)”.
–
91: The lowest input to OR #1 is operand “Virt Op 3 On".
–
90: The input just above the lowest input to OR #1 is operand “XOR(2)”.
–
89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.
–
88: The upper input to the XOR is operand “Virt Ip 1 On".
–
87: The input just below the upper input to OR #1 is operand “Virt Op 2 On".
–
86: The upper input to OR #1 is operand “Virt Op 1 On".
–
85: The last parameter is used to set the latch, and is operand “Virt Op 4 On".
The equation for virtual output 4 is:
[85] Virt Op 4 On
[86] Virt Op 1 On
[87] Virt Op 2 On
[88] Virt Ip 1 On
[89] DIG ELEM 1 PKP
[90] XOR(2)
[91] Virt Op 3 On
[92] OR(4)
[93] LATCH (S,R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR(3)
[98] TIMER 2
[99] = Virt Op 4
Now check that the selection of parameters produce the required logic by converting the set of parameters into a
logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check.
FlexLogic entry:
NOT
FlexLogic entry:
AND (2)
FlexLogic entry:
= Virt Op 3 (VO3)
97
98
99
FlexLogic entry:
Dig Element 2 (DE2) OP
FlexLogic entry:
Cont Ip 2 On (H1c)
95
96
AND
Virtual output 3
827030A2.CDR
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...