5-28
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
5.3.4 Communications
5.3.4.1 Menu
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
5.3.4.2 Serial ports
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
SERIAL PORTS
RS232 BAUD RATE
,
RS485 COM2 BAUD RATE
, and
PARITY
— The L60 is equipped with two independent serial communication
ports. The faceplate RS232 port is intended for local use and has two options for baud rate. The rear COM2 port is RS485
and has settings for baud rate and parity. It is important that these parameters agree with the settings used on the
computer or other equipment that is connected to these ports. Any of these ports can be connected to a computer
running the EnerVista software. This software can download and upload setting files, view measured parameters, and
upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer
using the RS485 ports. If IEC 60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid
parity is Even.
COMMUNICATIONS
SERIAL PORTS
See below
NETWORK
ROUTING
MODBUS PROTOCOL
PROTOCOL:
DNP 3.0
Range: DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
DNP PROTOCOL
DNP / IEC104
POINT LISTS
IEC 61850 PROTOCOL
Access in EnerVista
WEB SERVER
HTTP PROTOCOL
TFTP PROTOCOL
IEC 60870-5-104
PROTOCOL
IEC103
PROTOCOL
SERIAL PORTS
RS232 BAUD
RATE: 115200
Range: 19200, 115200
RS485 COM2 BAUD RATE:
19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200 bit/s
RS485 COM2 PARITY:
Even
Range: None, Odd, Even
RS485 COM2 RESPONSE
MIN TIME: 0 ms
Range: 0 to 1000 ms in steps of 10
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...