CHAPTER 5: SETTINGS
PRODUCT SETUP
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-23
5
Example:
If this setting is enabled and an attempt is made to change settings or upgrade the firmware, the UR device
denies the settings changes or denies upgrading the firmware. If this setting is disabled, the UR device accepts settings
changes and firmware upgrade.
This role is disabled by default.
FACTORY SERVICE MODE
— When Enabled, the device can go into factory service mode. For this setting to become enabled a
Supervisor authentication is necessary. The default value is Disabled.
SUPERVISOR ROLE
— When Enabled, the Supervisor role is active. To Disable this setting a Supervisor authentication is
necessary. If disabled, the Supervisor role is not allowed to log in. In this case, the Administrator can change the settings
under the Supervisory
menu.
If enabled, Supervisor authentication is required to change the settings in the Supervisory menu. If the Supervisor disables
their role after authentication, the Supervisor session remains valid until they switch to another role using MMI or until they
end the current Supervisor session if using communications.
This role is disabled by default.
SERIAL INACTIVITY TIMEOUT
— The role logged via a serial port is auto logged off after the Serial Inactivity timer times out. A
separate timer is maintained for RS232 and RS485 connections. The default value is 1 minute.
Self-tests
SETTINGS
PRODUCT SETUP
SECURITY
SUPERVISORY
SELF TESTS
FAILED AUTHENTICATE
— If this setting is Enabled then the number of failed authentications is compared with the Session
Lockout threshold. When the Session Lockout threshold is exceeded, this minor alarm indication comes up.
FIRMWARE LOCK
— If this setting is Enabled, then any firmware upgrade operation attempt when the Lock Relay setting is
enabled brings up this self test alarm.
SETTINGS LOCK
— If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self
test.
SETTINGS
PRODUCT SETUP
SECURITY
SUPERVISORY
SELF TESTS
FAILED AUTHENTICATE
CyberSentry setup
When first using CyberSentry security, use the following procedure for setup.
1.
Log in to the relay as Administrator by using the
VALUE
keys on the front panel to enter the default password
"ChangeMe1#". Note that the Lock Relay setting needs to be disabled in the
Security > Supervisory
menu. When this
setting is disabled, configuration and firmware upgrade are possible. By default, this setting is disabled.
2.
Enable the Supervisor role if you have a need for it.
3.
Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4.
Log out of the Administrator account by choosing None.
5.
Next, Device or Server authentication can be chosen on the login screen, but the choice is available only in EnerVista.
Use Device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator,
Observer). When using a serial connection, only Device authentication is supported. When Server authentication is
required, characteristics for communication with a RADIUS server must be configured. This is possible only in the
EnerVista software. The RADIUS server itself also must be configured. The appendix called RADIUS Server at the end of
this instruction manual gives an example of how to set up a simple RADIUS server. Once both the RADIUS server and
SELF TESTS
FAILED
AUTHENTICATE
See below
FIRMWARE LOCK:
Enabled
Range: Enabled, Disabled
SETTINGS LOCK:
Enabled
Range: Enabled, Disabled
FAILED
AUTHENTICATE
FAILED AUTHENTICATE:
Enabled
Range: Enabled, Disabled
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...