4-28
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
LOGIC DIAGRAMS
CHAPTER 4: INTERFACES
4
By default, when an incorrect Command or Setting password has been entered via any external communications interface
three times within five minutes, the
REMOTE ACCESS DENIED
FlexLogic operand is set to
“
On
”
and the L60 does not allow settings
or command access via the any external communications interface for five minutes. The
REMOTE ACCESS DENIED
FlexLogic
operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings password.
These default settings can be changed in EnerVista under
Settings > Product Setup > Security
.
4.3 Logic diagrams
Logic diagrams in this instruction manual provide an overview of function and settings. A logic diagram is based on
•
Inputs-on the left side, which are setting and operands
•
Logical gates, which is Boolean algebra to combine logical lines using AND, OR, NOT, and other gates to get a new
logical state
•
Logical operators, which are timers, one-shot operations, latches, and so on
•
Outputs-on the right side, which are products of the manipulations with inputs, logical gates, and logical operators to
produce new operands and define the output state of the element
True and false values are denoted by 1 and 0 respectively. A function usually is high/on/enabled when 1.
Reading from right to left in the following diagram, the
TRIP BUS 1 OP
and
TRIP BUS 1 PKP
FlexLogic operands on the right side
are triggered when either the settings or reset latch in the middle of the diagram is triggered. When this applies, the
TRIP
BUS 1 OP
operand is triggered after the delay set by the
TRIP BUS 1 PICKUP DELAY
or
TRIP BUS 1 RESET DELAY
setting, while the
TRIP BUS 1 PKP
operand initiates immediately. The settings or reset latch in the middle of the diagram is triggered as follows.
•
For the reset, one of three conditions are required to meet the OR requirement shown at the bottom left. That is, the
TRIP BUS 1 LATCHING
setting must be 0=Disabled (which is negated by the NOT function to become 1=Enabled), output
from the
TRIP BUS 1 RESET
FlexLogic operand must be 1, or output from the
RESET OP
FlexLogic operand must be 1.
•
For the settings, one of 16 input conditions at the top left must be met for the OR, the
TRIP BUS 1 FUNCTION
must be
Enabled, and the
TRIP BUS 1 BLOCK
output must output as 0, which is then negated/reversed by NOT to become 1.
Table 4-1: Logic diagram symbols
Symbol
Description
= Off
Output from FlexLogic operand, so user-defined
= Enabled
1 = Enabled and 0 = Disabled
OR
Any function input on the left side satisfies the condition
AND
All functions input on the left side are required to satisfy the condition
Not. Negates/reverses the output, for example 0 becomes 1.
Connection
S, R
Set, Reset
T
PKP
Timer pickup. Triggered by the settings latch in the diagram.
T
RST
Timer reset. Triggered by the reset latch in the diagram.
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...