5-40
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
The DNP improves upon many master-slave protocols by improving overall communication performance requirements
and provides time-stamping with millisecond accuracy.
The L60 supports the Distributed Network Protocol (DNP) version 3.0. DNP is enabled when the
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
PROTOCOL
setting is set to DNP 3.0. The L60 can be used as a DNP slave device connected to
multiple DNP masters (usually an RTU or a SCADA master station). Since the L60 maintains two sets of DNP data change
buffers and connection information, two DNP masters can actively communicate with the L60 at one time.
See the UR Series Communications Guide for more information on DNP.
The DNP Channels sub-menu is shown.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP PROTOCOL
DNP CHANNELS
The
DNP CHANNEL 1 PORT
and
DNP CHANNEL 2 PORT
settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, DNP is the only protocol running on that port; Modbus or IEC
60870-5-103 are disabled. If DNP is assigned to RS485, the protocol must be set to DNP on the serial port configuration as
well, for the change to take effect. When the
DNP CHANNEL 1(2) PORT
setting is set to “Network - TCP,” the channel 1(2) DNP
protocol can be used over TCP/IP on the Ethernet ports. When this value is set to “Network - UDP,” the DNP protocol can be
used over UDP/IP on channel 1 only.
Changes to these port settings take effect when power has been cycled to the relay.
The
DNP ADDRESS
setting is the DNP slave address. This number identifies the L60 on a DNP communications link. Assign a
unique address to each DNP slave.
The L60 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which
the L60 can connect. The settings follow.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP PROTOCOL
DNP NETWORK CLIENT ADDRESSES
The
DNP TCP/UDP PORT NUMBER
setting is for normal DNP operation. To close the port, set the port number to 0. The change
takes effect when the L60 is restarted.
The
DNP UNSOL RESPONSE FUNCTION
is set to “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The
DNP UNSOL RESPONSE TIMEOUT
sets the time the L60 waits for a DNP master to confirm an unsolicited
response. The
DNP UNSOL RESPONSE MAX RETRIES
setting determines the number of times the L60 retransmits an
unsolicited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The
DNP
UNSOL RESPONSE DEST ADDRESS
is the DNP address to which all unsolicited responses are sent. The IP address to which
solicited responses are sent is determined by the L60 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the L60 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the
DNP VOLTAGE SCALE FACTOR
setting is set to “1000,”
all DNP analog input points that are voltages are returned with values 1000 times smaller (for example, a value of 72000 V
on the L60 is returned as 72). These settings are useful when analog input values must be adjusted to fit within certain
DNP CHANNELS
DNP CHANNEL 1 PORT:
NONE
Range: NONE, COM2 - RS485, FRONT PANEL - RS232,
NETWORK - TCP, NETWORK - UDP
DNP CHANNEL 2 PORT:
NONE
Range: NONE, COM2 - RS485, FRONT PANEL - RS232,
NETWORK - TCP
NOTE
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
DNP NETWORK
CLIENT ADDRESSES
CLIENT ADDRESS 1:
0.0.0.0
Range: standard IP address
CLIENT ADDRESS 5:
0.0.0.0
Range: standard IP address
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...