CHAPTER 5: SETTINGS
SYSTEM SETUP
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-117
5
5.4.3.3 Disturbance detectors (internal)
The disturbance detector (ANSI 50DD) element is a sensitive current disturbance detector that detects any disturbance on
the protected system. The 50DD function is used directly in some elements in the relay, for example VT Fuse Failure
detector or Fault Report. It can also be used to supervise current-based elements to prevent maloperation as a result of
the wrong settings or external CT wiring problem. A disturbance detector is provided for each source.
The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector logic is as
follows.
Figure 5-47: Disturbance detector logic
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting
(
PRODUCT SETUP
DISPLAY PROPERTIES
CURRENT CUT-OFF LEVEL
) controls the sensitivity of the disturbance detector
accordingly.
5.4.3.4 Example for use of sources
An example of the use of sources is shown in the following figure. A relay can have the following hardware configuration:
This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
827092A3.CDR
SOURCE 1
CURRENT PHASOR
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
SOURCE 2
CURRENT PHASOR
SOURCE 6
CURRENT PHASOR
ACTUAL
SETTING
SETTING
SETTING
ACTUAL
ACTUAL
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
I
_1
I
_1
I
_1
SRC 1 50DD OP
SRC 2 50DD OP
SRC 6 50DD OP
I
_2
I
_2
I
_2
I
_0
I
_0
I
_0
OR
OR
OR
Where ’ is 2 cycles old
I
Where ’ is 2 cycles old
I
Where ’ is 2 cycles old
I
I
I
_1 - _1’ >2*CUT-OFF
I
I
_1 - _1’ >2*CUT-OFF
I
I
_1 - _1’ >2*CUT-OFF
I
I
_2 - _2’ >2*CUT-OFF
I
I
_2 - _2’ >2*CUT-OFF
I
I
_2 - _2’ >2*CUT-OFF
I
I
_0 - _0’ >2*CUT-OFF
I
I
_0 - _0’ >2*CUT-OFF
I
I
_0 - _0’ >2*CUT-OFF
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...