CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-251
5
This element is used to give a time-delay operating characteristic versus the applied fundamental voltage (phase-to-
ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite time element.
The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting selects the
minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage below
which the element is blocked (a setting of “0” allows a dead source to be considered a fault condition).
Figure 5-138: Phase undervoltage1 logic
5.6.14.3 Phase overvoltage (ANSI 59P, IEC PTOV)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
VOLTAGE ELEMENTS
PHASE OVERVOLTAGE1(3)
PHASE UV1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
PHASE UV1
EVENTS: Disabled
Range: Disabled, Enabled
PHASE
OVERVOLTAGE1
PHASE OV1
FUNCTION: Disabled
Range: Disabled, Enabled
PHASE OV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
PHASE OV1
PICKUP: 1.000 pu
Range: 0.000 to 3.000 pu in steps of 0.001
PHASE OV1 PICKUP
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PHASE OV1 RESET
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PHASE OV1 BLOCK:
Off
Range: FlexLogic Operand
PHASE OV1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
PHASE OV1
EVENTS: Disabled
Range: Disabled, Enabled
PHASE UV1
FUNCTION:
PHASE UV1
BLOCK:
PHASE UV1 SOURCE:
PHASE UV1 MODE:
PHASE UV1
PICKUP:
PHASE UV1
CURVE:
PHASE UV1
DELAY:
PHASE UV1
MINIMUM VOLTAGE:
Off = 0
Source VT = Delta
Phase to Ground Phase to Phase
RUN
RUN
VCG or VCA
PICKUP
VBG or VBC
PICKUP
VAG or VAB
Minimum
VBG or VBC
Minimum
VCG or VCA
Minimum
Source VT = Wye
VAG
VAB
VBG
VBC
VCG
VCA
Enabled = 1
VAB
VBC
VCA
PHASE UV1 A PKP
PHASE UV1 B PKP
PHASE UV1 C PKP
PHASE UV1 PKP
PHASE UV1 A DPO
PHASE UV1 B DPO
PHASE UV1 C DPO
PHASE UV1 A OP
PHASE UV1 B OP
PHASE UV1 C OP
PHASE UV1 OP
AND
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
827039AC.CDR
AND
AND
AND
OR
OR
<
<
<
<
<
}
t
V
t
t
V
V
VAG or VAB
PICKUP
<
RUN
PHASE UV1 DPO
FLEXLOGIC OPERAND
AND
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...