![GE Digital Energy L60 Скачать руководство пользователя страница 209](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854209.webp)
CHAPTER 5: SETTINGS
PRODUCT SETUP
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-79
5
The configuration menu allows a maximum of four ASDUs containing measurands.
Measurands are sent as a response to Class 2 requests, which are cyclic requests coming from the master.
TYPE IDENTIFICATION (TYP)
— The configuration field TYP indicates how many measurands are present in the corresponding
ASDU. Each ASDU can take either 4 or 9 measurands maximum, depending on the type identification (3 respectively 9).
FUNCTION TYPE (FUN)
and
INFORMATION NUMBER (INF)
— These two fields form the Information Object Identifier of the ASDU
as defined in IEC 60870-103.
SCAN TIMEOUT (SCAN TOUT)
— This is the cyclic period used by the L60 to decide when a measurand ASDU is included in a
response. The measurand is sent as response to a Class 2 request when the corresponding timeout expires. The default
value 0 means 500 ms.
ASDU 1 INF:
0
Range: 0 to 255 in steps of 1
ASDU 1 SCAN TOUT:
0
Range: 0 to 1000 s in steps of 1
ASDU 1 ANALOG 1
Off
Range: FlexAnalog parameter
ASDU 1 ANALOG 1
FACTOR: 1.000
Range: 0.000 to 65.535 in steps of 0.001
ASDU 1 ANALOG 1
OFFSET: 0
Range: -32768 to 32767 in steps of 1
ASDU 1 ANALOG 9
Off
Range: FlexAnalog parameter
ASDU 1 ANALOG 9
FACTOR: 1.000
Range: 0.000 to 65.535 in steps of 0.001
ASDU 1 ANALOG 9
OFFSET: 0
Range: -32768 to 32767 in steps of 1
ASDU 4
ASDU 4 TYP:
9
Range: 3 or 9
ASDU 4 FUN:
0
Range: 0 to 255 in steps of 1
ASDU 4 INF:
0
Range: 0 to 255 in steps of 1
ASDU 4 SCAN TOUT:
0
Range: 0 to 1000 s in steps of 1
ASDU 4 ANALOG 1
Off
Range: FlexAnalog parameter
ASDU 4 ANALOG 1
FACTOR: 1.000
Range: 0.000 to 65.535 in steps of 0.001
ASDU 4 ANALOG 1
OFFSET: 0
Range: -32768 to 32767 in steps of 1
ASDU 4 ANALOG 9
Off
Range: FlexAnalog parameter
ASDU 4 ANALOG 9
FACTOR: 1.000
Range: 0.000 to 65.535 in steps of 0.001
ASDU 4 ANALOG 9
OFFSET: 0
Range: -32768 to 32767 in steps of 1
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...