600-SERIES HARDWARE MANUAL
Appendix Q - 635 DPI Installation
APPENDIX-Page
Q-9
[STEP 6] 635 DPI PREP: SETTING JUMPERS FOR LOCK RELAYS
NOTES:
600 DPI only supported dry relay operation
635 DPI supports both
dry
relay and
wet
relay operation
Do not land lock power supply on the LPR terminal if using dry relays
REMOVE JUMPERS for DRY RELAY OPERATION
Board Section
Jumpers
DRY Operation
Section-1 / Door 1
15 & 16
removed
Section-2 / Door 2
17 & 18
removed
LOCK POWER:
DO NOT use the LPR contact
. Provide power at the lock.
See the section on
Wiring Lock Power for Dry Relays
INSTALL JUMPERS for WET RELAY OPERATION
Board Section
Jumpers
Wet Operation
Section-1 / Door 1
15 & 16
installed
Section-2 / Door 2
17 & 18
installed
LOCK POWER:
connect (separate) power supply to the LPR contact.
See the section on