600-SERIES HARDWARE MANUAL
Appendix Q - 635 DPI Installation
APPENDIX-Page
Q-2
INSTALL REQUIREMENTS
1.
WARNING:
Do Not Connect A 5v Reader Directly To The 635 DPI – you must install a voltage regulator
for 5v readers or configure the reader for 12v. The 635 DPI supports 12 volt readers directly connected.
2.
WARNING:
Failure to properly land lock wiring (using wet relay operation) can short lock power supply.
3.
CAUTION:
do not reset power to a DPI during the flashing process. This can damage the factory flash.
4.
You must flash the 600 CPU to v4.60
(or higher)
BEFORE you connect a 635 DPI
.
System Galaxy software SG 9.0.5 (or later) or SG 10.0 (or later) supports v4.60 flash.
5.
You must set a valid board ID on the 635 DPI.
Use the binary switch before powering up/connecting the
board. The factory default is ‘16’ (1-16 are supported).
If you are replacing a board you will use the ID of the board you are replacing so you don’t have
to reprogram the software. If adding a new board you will choose a board ID that is not used.
You can use either the Galaxy software or HyperTerminal if you need to determine the existing
board ID in case you are replacing an existing board.
You will need access to the System Galaxy software (server) to add the board to the database if
you are adding a new board / new doors.
6.
The following requirements apply to lock wiring and operation.
The 635 supports Fail Safe and Fail Secure
You must use install surge protection diodes
at the device-end of line (at the lock).
You must use a se12/+24 VDC power supply to power door Locks
.
Lock relays (“relay 1”) can be used in wet or dry operation (see next item)
7.
By default, all Relays are FORM-C SPDT DRY OUTPUT with Max. 24 VDC @ 1.5 amps.
a)
Dry Contact Relay Operation -
recommended if you are replacing a 600 DPI for service repair
Fail-safe and Fail-secure are supported under dry relay operation.
Remove lock jumpers. (J15 &16 sect 1; J17 & 18 sect 2)
Do not land lock power on the board – important to see diagram and install steps.
b)
Wet Contact Relay Operation
- is available (not mandatory) if you are adding a new board and wish to
use
wet relay operation.
You must install lock jumpers before you install the board. (J15 &16 sect 1; J17 & 18 sect 2)
You must correctly land lock power on the LPR contact (+12/+24 VDC).
You must correctly land lock wiring –
must
see diagrams for fail-safe / fail-secure lock wiring
.
WARNING
: failure to follow proper lock wiring for wet relay operation can short the lock power supply.
8.
Relay-2 always uses FORM-C SPDT DRY OUTPUT; Max. 24 VDC @ 1.5 amps. NO/NC supported.
9.
Door Contact Supervision is supported. You can change to a different value than the factory default.
Factory Default 4.7k ohm resistors are installed in the resistor sockets.
EOL resistors must match the value of the socketed on-board resistor.
EOL resistors should be place at the device end
EOL configurations supported are series, parallel, and series-parallel.
instructions for installing supervision resistors in Chapter 2 - 600 Hardware Guide