STEP 11. Walk-Test the System (recommended)
If you have not set up the minimal software programming required to walk-test the system, you
can turn to Step 9 and reference the Software Setup Quick Notes.
11.1 Quick Steps to Software Setup
More in-depth programming information is found the main SG Software Manual.
Table 33:
Software Setup - Process for 600 Loops are as follows
Step Action
1
Add the Cluster (Loop) in System Galaxy
in the Loop Properties screen or Loop Wizard
2
Add the Controller(s) in System Galaxy
in the Controller Properties screen or Wizard: At this
point the controller should automatically come online provided the core GCS Services are
running (i.e. Client Gateway, Communication Service, Event Service and DBWriter Service).
3
Add the DPI boards in System Galaxy
in the Controller Properties screen:
4
Program the Door/Reader
as needed in System Galaxy.
The Reader Properties are
primarily the same for the 600-series as for the 508i-series, thus refer to the main SG Software
Manual for details if needed.
5
Program any Cards, Schedules, Access Rules, Schedules, etc.
This functionality and
programming is described in the Software Manual.
6
Add the DIO boards in System Galaxy
in the Controller Properties screen:
7
Add the DSI board(s) in SG in the controller properties screen. Also you must configure
the DSI Channels in the Hardware Programming screen to the appropriate output type
(i.e. Cypress Clock mode, General Output mode, or Elevator Output mode)
8
Add The Inputs In System Galaxy
In The Input Properties Screen: Inputs Are Programmed
As Normal (See SG Software Manual) with the exception of Supervision and Hypervision.
9
Program any I/O Groups and Outputs in System Galaxy:
Refer to the main System Galaxy
Software Manual for the details on programming these features.
10
Verify Services are running and that the 600 Controller is connected to the Event
Service – this section includes basic instructions.
More detailed instructions about the
Event Service are found in Chapter 5 of this manual. Also, instructions about core GCS
Services are found in Chapter 11 of the main System Galaxy Software Manual.
11
Verify / Load Flash and then Data to Controllers:
This is done through the GCS Loader.
The loader can be started from the SG Hardware Tree by right clicking a loop.
12
Walk-Test the System:
walk test the loops with a test card (see Step 12.2). Likewise
alarm cards and other inputs can be tested in the same fashion.
If you find any input,
output, reader or other device not functioning correctly, then verify your device programming,
schedules and access rules are correctly configured, applied/loaded.