600-SERIES HARDWARE MANUAL
Appendix P - Setting LCD Unit IDs
P
– Appendix: Configuring LCD Unit ID
YOU MUST USE THE V 1.77 Galaxy
Configuration Programming Tool
to configure the LCD
Display UNIT IDs.
Valid Unit IDs are 1 through 16
the DSI supports 16 max. units per 485 port
See the Config Tool Manual for full operating instructions.
P.1
: Configure the LCD Unit ID
IMPORTANT: YOU MUST CONFIGURE ONE UNIT AT A TIME
1.
Choose the Configuration option under the DSI board
2.
Set the Configuration to LCD 4X20 Display Module
3.
Select Test LCD option and allow the unit time to respond
4.
Choose the existing address in the Old Address droplist
5.
Choose the address you wish to set in the New Address droplist
6.
Click CHANGE ADDRESS button to set the LCD Unit ID
APPENDIX-Page
P-1