600-SERIES HARDWARE MANUAL
Appendix H - HyperTerminal Commands
APPENDIX-Page H-6
Setting the Loop and Controller ID’s:
Use templates found in Appendix -A to record hardware configurations. Copy as needed,
6.
Set Cluster/Loop ID: this value must be “1” (one) or greater.
All CPU’s in the same cluster/ loop will have the same Loop ID
.
The Loop ID here must match the Loop ID set in the software/database.
NOTE:
if the Loop has already been programmed into the software/database you should
set this field to match the software. You can find this information in the System Galaxy
Loop Properties screen.
7.
Set the Unit ID: this value must be “1” (one) or greater.
The Unit ID must be unique for all panels within the same loop.
The Unit ID must match the Unit ID used in the software/database.
NOTE:
if Controller has already been programmed into the software/database you should
set this field to match the software. You can find this information in the System Galaxy
Controller Properties screen.
8.
Set the CPU Number: this value should be “1”.
Note:
If you are setting up a second (dual) CPU, then you will set this value to “2” (two) for
the second CPU in the controller.