13 Pulse 3 Time
This timer controls the active duration (0-255 minutes) of outputs
programmed with both the
“Pulse 1” and “Pulse 2” attribute
s.
Default = 10 minutes.
14 Delay 1 Time
This timer controls the switch on delay (0-255 seconds) of outputs
programmed with the “Delay 1” attribute. Default = 10 seconds.
15 Delay 2 Time
This timer controls the switch on delay (0-255 seconds) of outputs
programmed with the “Delay 2” attribute. Default = 30 seconds.
16 Delay 3 Time
This timer controls the switch on delay (0-255 minutes) of outputs
programmed with both the “Delay 1” and “Delay 2” attributes.
Default = 10 minutes.
17 Warning Delay
This timer controls the delay (0-255 seconds) in which zones
programmed as “Warning” must remain active before a warning
tone is generated. Default = 60 seconds.
18 Radio Polling Delay
This timer controls the delay (0-255 minutes) in which all wireless
devices must poll into the system. If any wireless device fails to poll
in within this period a fault is generated for the device. Default = 60
minutes.
19 Random Minimum Time
This timer controls the minimum on/off time (0-255 minutes) for
the “Random On/Off” output type. Default = 1 minute.
20 Random Maximum Time
This timer controls the maximum on/off time (0-255 minutes) for
the “Random On/Off” output type. Default =
10 minutes.
21 Access Time
This timer controls the on time (0-255 seconds)
of the “
User
Access”
output type. Default = 7 seconds.
22 Keyswitch Auto Re-arm Time
This timer controls auto re-arm time (0-255 minutes) for an area
disarmed by a keyswitch. When an area is disarmed by a keyswitch,
this timer is started and if a zone in the area is activated the timer is
reset. When there has been no activity in the area and the timer
expires, the area is automatically armed.
The “Auto Arm” must be
enabled in Area Options 3, see page 23. Default = 5 minutes.
23 Auto Re-arm Time
This timer controls auto re-arm time (0-255 minutes) for an area
disarmed by a user code. When an area is disarmed, this timer is
started and if a zone in the area is activated the timer is reset. When
there has been no activity in the area and the timer expires, the
area is automatically armed. The “Auto Arm” must be enabled in
Area Options 3, see page 23. Default = 15 minutes.
24 Chime View Time
This timer is used to control the duration (0-255 seconds) of the
visible chime activation. Default = 60 seconds.
System Counters
The system counters are used to limit the number of times a
function or feature can be carried out.
Locations:
3201
- Auto Rearm Counter.
3202
- Number of Remote Resets.
3203
- Zone Count Warning.
3204
- Zone Count Logging.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in 3 digit counter value. When finished press
Enter
to accept or
Clear
to cancel.
01 Auto Rearm Counter
This counter controls the number of times (0-255) a zone can rearm
during an armed period. Once a zone has reached its rearm limit, it
is locked out so that it cannot cause further alarm activations during
the same armed period. Default = 3.
02 No of Remote Resets
This counter controls the number of times (0-255) the UDL software
can be used to reset the system remotely before an engineer must
attend site. Default = 0.
03 Zone Count Warning
This counter controls the number of times (0-255) that a zone must
activate, before triggering the corresponding “Zone ## Count”
output. Default = 0.
04 Zone Count Logging
This counter controls the number of times (0-255) that a zone must
activate, before logging a “Zone Count ##” event in the system log.
Default = 0.
05 Time Zone
This counter set the Time Zone, 0 = GMT. Default = 2.
Hardware - Volume Levels
This set of options controls the volume levels for each group of
system tones.
Locations:
3301
- Panel Speaker Volume.
3302
- Chime Volume.
3303
- Advisory Tone Volume.
3304
- Alarm Tone Volume.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in 3 digit level. When finished press
Enter
to accept or
Clear
to
cancel.
01 Panel Speaker Volume
This option controls the level (0-10) of the exit, entry, fault and
warning tones from the control panel speaker. Default = 5.
02 Chime Volume
This option controls the level (0-10) of the chime tone from the
control panel speaker. Default = 5.
03 Advisory Tone Volume
This option controls the level (0-10) of the advisory tones from the
control panel speaker. Default = 5.
04 Alarm Tone Volume
This option controls the level (0-10) of the alarm tones from the
control panel speaker. Default = 10.
Hardware - Output Monitoring
This option enables/disables fault monitoring of the control panel
outputs.
Locations:
3310
Entry Mode:
Enter 4 digit location followed by
Enter
, then use
keys
1
to
4
to toggle options from the list below on or off. When
finished press
Enter
to accept or
Clear
to cancel.
1
Panel Output 1 (Bell)
On: The output is monitored for faults.