FSK-RAP816-V2015.04
21
6
Remote Detector Test
On: Zones with this attribute are monitored for specific activity
during the remote detector test. The detector must be
connected to the control panel using triple EOL wiring and the
detector remote test input must be connected to a panel
output programmed as “Remote Detector Test”
.
Off: The zone functions as normal.
7
Momentary Keyswitch
On: If the zone type is a keyswitch type, the operation mode is
changed to momentary.
Off: If the zone type is a keyswitch type, the operation remains as
latching mode.
8
Record Activity
On: Zone activity will be recorded against the zone counter.
Off: Zone activity does get recorded.
Zone Areas
The Rhino 816 has 2 areas which allow the system to be divided into
different areas of protection. Each area can be armed and disarmed
independently from each other. By default all zones are assigned to
area 1, but if required a zone can be assigned to either area. If a
zone is assigned to more than one area it will only be armed when
all assigned areas are armed.
Locations:
1401
to
1416
Zone 01 to 16: Areas.
Entry Mode:
Enter 4 digit location followed by
Enter
, then use
keys
1
to
2
to toggle options from the list below on or off. When
finished press
Enter
to accept or
Clear
to cancel.
1
Area 1
On: The zone is assigned to area 1.
Off: The zone is not assigned to area 1.
2
Area 2
On: The zone is assigned to area 2.
Off: The zone is not assigned to area 2.
Zone Bypass Options
Each zone can have one or more optional bypass attributes
programmed to control when the zone is bypassed.
Locations:
1501
to
1516
Zone 01 to 16: Zone Bypass Options.
Entry Mode:
Enter 4 digit location followed by
Enter
, then use
keys
1
to
6
to toggle options from the list below on or off. When
finished press
Enter
to accept or
Clear
to cancel.
1
In Stay 1
On: The zone is bypassed when Stay 1 arming mode is selected.
Off: The zone is not bypassed when Stay 1 arming mode is
selected.
2
In Stay 2
On: The zone is bypassed when Stay 2 arming mode is selected.
Off: The zone is not bypassed when Stay 2 arming mode is
selected.
3
In Stay 3
On: The zone is bypassed when Stay 3 arming mode is selected.
Off: The zone is not bypassed when Stay 3 arming mode is
selected.
4
Manual
On: The zone can be bypassed by the user when arming the
system.
Off: The zone cannot be bypassed by the user.
5
Auto Bypass
On: The zone is automatically bypassed at the end of exit mode if
the zone is still active.
Off: The zone is not bypassed at the end of exit mode, and the
system will fail to arm if the zone remains active.
6
Keyswitch Bypass
On: The zone is bypassed
when a “Bypass Key” zone type is active
and reinstated when the “Bypass Key” is secure
.
Off: The zone is not bypassed when a Bypass Key is operated.
Zone Chime
Each zone can have an optional chime mode programmed that
allows the panel and remote keypads to generate an audible tone
when the zone is activated in the disarmed mode.
Locations:
1601
to
1616
Zone 01 to 16: Zone Chime.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in 1 digit chime option from list below or press
i
to scroll through
list. When finished press
Enter
to accept or
Clear
to cancel.
0
Off
The zone will not generate a chime tone.
1
Tone 1
The zone generates chime tone 1 when activated in the disarmed
mode.
2
Tone 2
The zone generates chime tone 2 when activated in the disarmed
mode.
3
Tone 3
The zone generates chime tone 3 when activated in the disarmed
mode.
4
Reserved
Do not use this option.
5
Visible and Tone 1.
The zone generates chime tone 1 and displays the activated zone on
the remote keypad when activated in the disarmed mode.
Zone Soak Test
Each zone can be put on test for a programmed soak test period.
When a zone is on test it will not cause an alarm if activated, but the
system will record the failure in the event log and indicate the fault
to the user.
Locations:
1701
to
1716
Zone 01 to 16: Zone Soak Test.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in a 1 digit soak test option from list below or press
i
to scroll
through list. When finished press
Enter
to accept or
Clear
to cancel.
0
No
The zone is not on soak test.
1
Yes
The zone is on soak test.
Zone Text
Each zone can be assigned a 20 character label that is displayed on
LCD remote keypads when viewing the zone status and event log.