Single EOL - N/C
This wiring configuration should be used when connecting detection
devices that only have a normally closed alarm output. Connect the
detector as shown below and ensure that the zone is programmed
for “
Single EOL
–
N/C
” operation, see
page 20.
Double EOL
This wiring configuration should be used when connecting detection
devices that have a normally closed alarm and tamper output.
Connect the detector as shown below and ensure that the zone is
programmed for “Double EOL” operation, see page
20.
Triple EOL
This wiring configuration should be used when connecting detection
devices that support triple EOL configuration, this will allow the
system to monitor alarm, tamper fault and mask. Connect the
detector as shown below and ensure that the zone is programmed
for “Triple EOL” operation, see
page 20.