FT-111(D) Panel Weighing Indicator, Technical Manual, Rev.1.0.0, May 2019
Page
129
of
146
Expanded Command List
Here 1
st
Dword (Input) is the data receiving from PLC and the “B23 … B16” bits describe below.
Bit No
Description
B23…B16
Expanded
Commands
List
Bin
Dec
Commands
00000000
0
R
Voltage of power supply
(2)
The value is indicated with 0.1 VDC increment
for DC variant.
00000001
1
R
Load cell millivolt value
(2)
(Only FT-111 )
Millivolt of active scale is indicated with 0.01
mV increment.
00000010
2
R
Command status
(2)
Dec
Descr. of 1st Dword
0
None
1
Command is processing
2
Command is done
3
Command failed
00000011
3
R/W
Reprint the last
label
(1) (2)
0
None
1
Reprint the last label
00000100
4
R/W
High resolution
(1) (2)
0
Enable
1
Disable
00000101
5
W
Unit change
(1)
0
From first to second unit
1
From second to first unit
00000110
6
R/W
Key lock
(1) (2)
0
Enable
1
Disable
00000111
7
W
Dynamic
operation
(1)
0
Dynamic reset
1
Dynamic start
0000100000
001011
8
11
Not used
00001100
12
R/W
Basic Peak
0
Enable
1
Disable
00001101
13
R/W
Hold
0
Enable
1
Disable
00001110
00111110
14
62
Not used
00111111
63
R/W
Dynamic filter
(1) (2)
Refer to par. 332 page 57
01000000
64
R/W
Filter
(1) (2)
0
No
1
Very Low
2
Low
3
Medium
4
High
5
Very High
01000001
65
R/W
Power on zero
(1) (2)
0
Disable
1
± %2
2
± %2LK
3
± %10
4
+ %15, - %5
5
± %20
01000010
66
R/W
Zeroing Range
(1) (2)
0
Disable
1
± 2%
2
± 3%
3
± 20%
4
± 50%
01000011
67
R/W
Auto Zero
Tracking
(1) (2)
0
Disable
1
± 0,3d
2
± 0,5d
3
± 1d
4
± 2d
5
± 3d
01000100
68
R/W
Tare
(1) (2)
0
No
1
Multi tare
2
Tare only at gross
01000101
69
R/W
Stability
Detection
Range
(1) (2)
0
± 0,3d
1
± 0,5d
2
± 1d