FT-111(D) Panel Weighing Indicator, Technical Manual, Rev.1.0.0, May 2019
Page
120
of
146
LINK/Activity LED
LED State
Description
Off
No link.
Green
Link, no traffic.
Green, flashing
Link and traffic.
Data Format
Data format of weight value can be programmable for Floating point (IEEE 754) or Integer. Refer to parameter
[ 191 ].
XDD Configuration
Powerlink data structures consist of 2 pcs Input-2 words and 2 pcs Output-2 words.
XDD configuration
for PLC
Figure 10.9
– Configuration of module properties with XDD file
Data Length
Description
1_Dword_Input_I2001_S01
1
st
Dword (FT-111 Output to PLC Input
2_Dword_Input_I2001_S02
2
nd
Dword (FT-111 Output to PLC Input)
1_Dword_Output_I2002_S01Out
1
st
Dword (PLC Output to FT-111 Input)
2_Dword_Output_I2002_S02Out
2
nd
Dword (PLC Output to FT-111 Input)
Powerlink Data Structure
For the Data Structure for Powerlink see Appendix 1,
page 123