Pn008
316C
Initial Display Selection When
Power On
0 to 9999
-
0010
After restart
Set the displayed Un Number when power on the device.
For example, set this parameter to 0, the display is Un000 after powering on the device.
Pn009
316D
Application Function
Selections 9
0000 to 0001
-
0000
After restart
Pn009.0: Shared DC Bus Function
0
Disabled.
1
Enabled.
Pn009.1: Reserved setting (Do not change).
Pn009.2: Reserved setting (Do not change).
Pn009.3: Reserved setting (Do not change).