background image

Products

Solutions

Services

Operating Instructions

Prothermo NMT532

Average temperature device

BA01032G/00/EN/22.19

71440635

2019-05-23

Содержание Prothermo NMT532

Страница 1: ...Products Solutions Services Operating Instructions Prothermo NMT532 Average temperature device BA01032G 00 EN 22 19 71440635 2019 05 23...

Страница 2: ...Prothermo NMT532 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Страница 3: ...Flexible tube handling 20 5 5 Mounting NMT532 on fixed roof tank 21 6 Electrical connection 32 6 1 Terminal connection 32 6 2 NRF590 terminals 34 6 3 Grounding 35 7 Adjustment and settings 36 7 1 Loca...

Страница 4: ...tuation will result in a risk of serious or fatal injury fire or explosion CAUTION Note This symbol alerts you to a dangerous situation Failure to avoid this situation will result in a risk of minor o...

Страница 5: ...processes or actions that are permitted Preferred Procedures processes or actions that are preferred Forbidden Procedures processes or actions that are forbidden Tip Indicates additional information R...

Страница 6: ...s Hazardous area Indicates the hazardous area Safe area non hazardous area Indicates the non hazardous area 1 2 6 Device symbol Symbol Meaning Safety instructions Observe the safety instructions conta...

Страница 7: ...nformation that is required during various phases of the life cycle of the device from product identification incoming acceptance and storage to mounting connection operation and commissioning through...

Страница 8: ...materials Depending on the version ordered the device can also be used with potentially explosive flammable poisonous or oxidizing materials Devices that are used in hazardous areas have correspondin...

Страница 9: ...mitted Observe local national regulations pertaining to repair of an electrical device Use only original spare parts and accessories from Endress Hauser Ex area Observe the following notes to eliminat...

Страница 10: ...nts Measured variable Temperature conversion range 200 to 100 C 328 to 212 F Measuring range 200 to 100 C 328 to 212 F Output signal Local HART protocol multi drop local HART loop connection Alarm sig...

Страница 11: ...ic pressure head in the 50 m 164 ft range in petroleum chemical product applications Data transmission Minimum cable diameter 24 AWG Cable type Twist pair with a shield Weight Approx 8 kg Conditions N...

Страница 12: ...tocol b Power supply c Local HART Ex i loop data transmission d Level e Gas temperature f Liquid temperature 1 Tankvision 2 NMS8x 3 NMT532 Typical application of NMT532 and NMS8x NMT532 is used most e...

Страница 13: ...receives radar level data from NRF81 and then calculates liquid and gas phase average temperature Calculated and standard data including temperature element raw data and device status are transmitted...

Страница 14: ...ial numbers from nameplates into the W M Device Viewer www endress com deviceviewer all information on the device will be displayed Enter serial numbers from nameplates into the Endress Hauser Operati...

Страница 15: ...T Ga Gb IECEx KEM 10 0058 Ambient temperature 40 C Ui 30 V li 120 mA Pi 1 W Ci 7 9 nF Li 48 H Warning Don t modify parts and circuits of this instrument Endress Hauser Yamanashi Co Ltd Yamanashi 406 0...

Страница 16: ...IS Cl I Zone 0 Ex ia IIB T Ga US IS Cl I Div 1 Gp C D T Cl I Zone 0 AEx ia IIB T Ga NI Cl I Div 2 Gp C D T C FM17CA0088 US FM17US0168 T T Installation par dessin de contr le C Ex462 875 2 US Ex461 852...

Страница 17: ...CE Risk of injury Transport the measuring device to the measuring point in its original packaging Take into account the center of gravity of the device in order to avoid unintended tilting Comply with...

Страница 18: ...ions of NMT532 10 0 39 26 1 02 142 5 5 61 1 2 3 4 215 8 46 A0038592 8 Dimensions of NMT532 Unit of measurement mm in 1 SUS304 2 Temperature probe SUS316L see tips below 3 Bottom hook SUS316 4 SUS316 T...

Страница 19: ...100 3 94 a NMT532 C 400 15 75 NMT532 D F NMT532 B A0038597 9 Element No 1 position a Height below the flange to the end of the temperature probe for all types of NMT532 5 3 Unpacking Unpack NMT532 wi...

Страница 20: ...minimum of 600 mm 23 62 in or more When installing the temperature probe onto a tank or if it is necessary to bend the temperature probe ensure that the bent portion is at least R 300 mm 11 8 in or m...

Страница 21: ...lexible tube and the bottom of the tank may vary depending on the type of heating coil 5 5 1 Top anchor method The flexible tube is fixed with a wire hook and a top anchor 26 1 02 1 2 3 4 6 5 a b 8 A0...

Страница 22: ...tom of the tank 5 Secure the tensioning wire twice through the hole at the bottom hook 6 Tighten the tensioning wire 7 Wind the provided wire around the tensioning wire to secure the tensioning wire 1...

Страница 23: ...2 Rotate the nuts clockwise until the top anchor s spring is 35 to 37 mm 1 38 to 1 46 in 35 37 1 38 1 46 A0038513 15 Top anchor installation 2 Unit of measurement mm in 13 Cover the top anchor This co...

Страница 24: ...low bottom hook 6 Approx 500 mm 20 in From the bottom of the tank to the temperature element position 1 Thermo well attachment procedure The flexible tube must be lowered carefully without overbending...

Страница 25: ...cified 3 Flange 4 Nozzle height 5 Tank height 6 Upper temperature element 7 Flexible tube LCAUTION Installation of an anchor weight Using an anchor weight that is heavier than 16 kg may cause internal...

Страница 26: ...t procedure 2 3 4 5 1 1 5 2 3 4 A B A0038601 18 Anchor weight attachment A Anchor weight high profile B Anchor weight low profile 1 Provided wire 2 Flexible tube 3 Bottom hook 4 Tensioning wire 5 Anch...

Страница 27: ...0038602 19 Floating roof tank Unit of measurement mm in a 400 mm 15 57 in Clearance of the bottom hook b 100 to 150 mm 3 94 to 5 91 in c 500 to 1000 mm 19 69 to 39 37 in Electrical compartment Cable e...

Страница 28: ...t mm in a Stilling pipe 50 8 mm 2 in or more depending on specifications b 400 mm 15 57 in Clearance of bottom hook c 500 to 1000 mm 19 69 to 39 37 in 1 Electrical compartment 2 Cable entry as specifi...

Страница 29: ...ture element 8 Guide ring LCAUTION Installation of an anchor weight Using an anchor weight that is heavier than 16 kg may cause internal damages to the flexible tube Ensure that the anchor weight is s...

Страница 30: ...hook twice and also tie the other end to the bottom hook 5 Wind the provided wire around both ties of the hooks to secure the tensioning wire 6 Using the bolts fix the mounting flange of NMT532 to th...

Страница 31: ...tion maintenance chamber 7 NMT532 8 Thermo well If the pressure inside a tank exceeds the atmospheric pressure absolute pressure 1 bar 100 kPa 14 5 psi install a thermo well protective pipe with no ho...

Страница 32: ...vice layout 2 1 A H2 H2 H1 H1 FG A0038528 24 NMT532 terminal ATEX Ex ia A Temperature data NMT532 intrinsically safe 2 wire HART communication see Information 1 Shielded twisted pair wire or steel arm...

Страница 33: ...0 60 Hz or DC20 62 V AC20 55 V b Non intrinsically safe HART communication NRF etc c Digital output Modbus RS485 serial pulse or HART d Alarm contact point e Operation contact point input f 4 to 20 mA...

Страница 34: ...ally safe local HART terminals RTD 24V mA 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 D S S D OPT1 OPT2 OPT3 OPT4 H H H P 4 3 2 1 A C B A0038533 27 NRF590 intrinsically safe terminals A A HART sen...

Страница 35: ...l and analog I O 6 3 Grounding NMT532 must be grounded to the tank potential before communication and power connections are made The connections from ground terminal of NMT532 to the tank ground must...

Страница 36: ...ure measurement 0 Converter only 1 Temperature converter These four types of basic data are available as standard Average liquid temperature Average gas temperature Level VH02 measured distance Device...

Страница 37: ...e indicated in GVH010 Liquid temp GVH441 Gas temp Displays the same value indicated in GVH013 Gas temp GVH442 Level The liquid level collected from NMS5 NMS7 is selected as either GVH000 Level Displac...

Страница 38: ...is only used to change the theoretical element position within NMT532 s software for average temperature calculation The physical positions of the elements will not change GVH486 Bottom point Sets th...

Страница 39: ...t be set to default before connecting to NMT532 Setting procedure 1 From the Expert menu choose Input Output HART device HART device s NMT device configuration 2 Select Yes for Config device 3 Enter t...

Страница 40: ...ion Operation Temperature NMT element values Element temperature Element position 1 to 24 Description Displays the position of the selected temperature element in the NMT Additional information Read a...

Страница 41: ...evice Access code Total no element Bottom point Temp elem short Temp elem open Output at error Gain adjust Kind of interval Element interval Element setup Select element Zero adjust Element temp Eleme...

Страница 42: ...al number of elements that can be configured Additional information Read access Operator Write access Bottom point Item Details Navigation Expert Input Output HART device HART device s MenuName HART D...

Страница 43: ...d opens Selection OFF ON Additional information Read access Operator Write access Maintenance Gain adjust Item Details Navigation Expert Input Output HART device HART device s MenuName HART device con...

Страница 44: ...4734 Description The element to be configured is manually selected Input unit 1 16 Factory setting 1 Additional information Read access Operator Write access Maintenance Zero adjust Item Details Navig...

Страница 45: ...s Navigation Expert Input Output HART device HART device s NMT device configuration Element configuration Element position 14738 Description Adjusts the element position Input unit Numerical value Fac...

Страница 46: ...184 is designed for the temperature measurement function Available parameters and functions are as follows The description of parameters is based on the FieldCare display screen The HART device code...

Страница 47: ...ing when shipping from the factory 8 3 2 Temperature measurement elements 1 VH10 to VH15 VH16 to 19 are not available in NMT 532 Code Display Details VH10 19 Temperature 1 10 Temperature of elements 1...

Страница 48: ...No 4 4 0 C 39 2 F T4 3 Element No 3 2 0 C 35 6 F T3 4 Element No 2 3 0 C 37 4 F T2 5 Element No 1 3 5 C 38 3 F T1 Advanced calculation method Average temperature is calculated by adding a corrective f...

Страница 49: ...0 C 35 6 F x 4 2 3 4 2 67 C 36 8 F In the diagram below represents V volume factor 3 5 C 38 3 F x 2 3 0 C 37 4 F x 3 2 0 C 35 6 F x 4 2 3 4 2 67 C 36 8 F 2 0 C 2 0 C 2 0 C 2 0 C 3 0 C 3 0 C 3 0 C 3 5...

Страница 50: ...6 1 F T5 4 Pt100 element No 4 24 C 75 2 F T4 5 Pt100 element No 3 26 0 C 78 8 F T3 6 Pt100 element No 2 25 5 C 77 9 F T2 7 Pt100 element No 1 25 0 C 77 0 F T1 8 Input signal cable 9 Probe bottom 8 3 4...

Страница 51: ...the matrix parameter to the default setting VH48 Gas Offset Gas offset Item type Read Write Default 300 mm 11 81 in Range 0 to 99999 mm When a temperature element in the gas vapor phase is within the...

Страница 52: ...81 in Default 1 To NMT532 converter 2 Temperature element 3 Gas phase 4 Exclusion range see Note 5 Level 6 Liquid phase 7 To tank bottom Although temperature elements in this range are in the liquid p...

Страница 53: ...lculations for details see VH26 Selec Ave Method 8 3 7 Operation power adjustment VH60 to VH69 Code Display Details VH67 Common Voltage Common voltage Item type Read only Range 0 to 255 0 to 3 V Displ...

Страница 54: ...ured values VH73 Temperature X Temperature X Item type Read only Temperature of the elements that were selected in VH70 Also displays each temperature measurement element that was displayed in VH10 VH...

Страница 55: ...he number of resistance samplings from all temperature measurement elements can be changed including that of the reference resistance installed on the circuit of the main unit Increasing the sampling...

Страница 56: ...type Read Write Default 2 Range 1 to 16 The number of available temperature measurement elements is entered This function is mainly used with the NMT532 Do not change the default parameter on the NMT...

Страница 57: ...to 99999 mm The position of the bottom point element from the tank bottom element No 1 is entered If Equal interval has been selected in VH85 the position of element No 1 is extremely important as th...

Страница 58: ...messages are sent to the host gauge As a result the error codes of VH88 and VH89 will appear on the host gauge s default screen and sent to the upper receiver as well VH93 Custody Mode Custody mode I...

Страница 59: ...or on Process for entering 876 5 mm 34 51 in example as a WB value 1 Enter 129 in Device Specific Commands 2 Enter 047 0x047E VH50 in Data Hex 047E indicates variable address 1150 3 Enter float value...

Страница 60: ...le in average liquid temperature calculations Refer to the following figures for Case 1 and Case 2 in the following table Case Application to average temperature calculation for temperature element 1...

Страница 61: ...his range none of the temperature elements will be used in average liquid temperature calculations 8 5 1 Temperature adjustment VH92 The following table shows the settings VH92 setting Presence of liq...

Страница 62: ...itch a To NMT532 CPU CN3 8 7 Module configuration After replacing the electric housing module parameters must be re entered manually into the electric housing module to maintain proper operation Check...

Страница 63: ...mperature element orange 9 4 element open The cable for a temperature element 4 is open Check the module s connections and check the impedance between the common cable white black or white purple and...

Страница 64: ...fect RAM Data memory is defective Replace the module 42 Memory defect EEROM Non volatile data memory is defective Replace the module Error codes appear on the screen when FieldCare is properly connect...

Страница 65: ...ning the exterior of measuring devices always use cleaning agents that do not attack the surface of the housing or the seals 10 2 Endress Hauser services Endress Hauser offers a wide variety of servic...

Страница 66: ...n ordering a spare part note the device designation on the nameplate Only replace parts with identical parts Carry out repairs according to the instructions On completion of repairs perform the specif...

Страница 67: ...to follow certain procedures when handling returned products that have come into contact with measured materials To ensure safe swift and professional device returns refer to the procedure and conditi...

Страница 68: ...erature measurement position will be set at approx 500 mm above the tank bottom When installing a high profile anchor weight from a nozzle at the top of the tank ensure that the nozzle opening is at l...

Страница 69: ...it of measurement mm in Description Details Weight JIS SS400 mild carbon steel Eye bolt JIS SS400 mild carbon steel Mass 12 kg 26 46 lb 12 1 3 Wire hook Wire hooks come in a variety of wire types size...

Страница 70: ...1 threaded connection It can accommodate different thread sizes materials and special specifications A joint flange is also possible 190 7 48 52 2 05 a A0038538 45 Top anchor dimensions Unit of measur...

Страница 71: ...sured materials 8 Declaration of Conformity 9 Return 67 Maintenance 65 Requirements for personnel 8 C CE mark 9 Cleaning Exterior cleaning 65 D Designated use 8 Disposal 67 E Endress Hauser services M...

Страница 72: ...www addresses endress com...

Отзывы: