Proline Cubemass C 100 HART
Commissioning
Hauser
69
10.2.10 Configuring the partial filled pipe detection
The
Partially filled pipe detection
submenu contains parameters that have to be set for
configuring empty pipe detection.
Navigation
"Setup" menu → Partially filled pipe detection
Partially filled pipe detection
→
Assign process variable
Low value partial filled pipe detection
High value partial filled pipe detection
Response time part. filled pipe detect.
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Assign process variable
–
Select process variable for
partially filled pipe detection.
• Off
• Density
• Reference density
Off
Low value partial filled pipe
detection
One of the following options is
selected in the
Assign process
variable
parameter:
• Density
• Reference density
Enter lower limit value for
deactivating partialy filled pipe
detection.
Signed floating-point
number
Country-dependent:
• 0.2 kg/l
• 12.5 lb/ft³
High value partial filled pipe
detection
One of the following options is
selected in the
Assign process
variable
parameter:
• Density
• Reference density
Enter upper limit value for
deactivating partialy filled pipe
detection.
Signed floating-point
number
Country-dependent:
• 6 kg/l
• 374.6 lb/ft³
Response time part. filled pipe
detect.
One of the following options is
selected in the
Assign process
variable
parameter:
• Density
• Reference density
Enter time before diagnostic
message is displayed for
partially filled pipe detection.
0 to 100 s
1 s