Commissioning
Proline Cubemass C 100 HART
58
Hauser
Parameter overview with brief description
Parameter
Description
Selection / User entry
Factory setting
Assign current output
Select process variable for current output.
• Off
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
• Density
• Reference density
• Concentration
• Dynamic viscosity
• Kinematic viscosity
• Temp. compensated
dynamic viscosity
• Temp. compensated
kinematic viscosity
• Temperature
• Carrier pipe temperature
• Electronic temperature
• Oscillation frequency 0
• Oscillation frequency 1
• Oscillation amplitude 0
• Oscillation amplitude 1
• Frequency fluctuation 0
• Frequency fluctuation 1
• Oscillation damping 0
• Oscillation damping 1
• Tube damping fluctuation 0
• Tube damping fluctuation 1
• Signal asymmetry
• Exciter current 0
• Exciter current 1
• Sensor integrity
Mass flow
Mass flow unit
Select mass flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Unit choose list
Country-specific:
• kg/h
• lb/min
Volume flow unit
Select volume flow unit.
Result
The selected unit applies for:
• Output
• Low flow cut off
• Simulation process variable
Unit choose list
Country-specific:
• l/h
• gal/min (us)
Current span
Select current range for process value output
and upper/lower level for alarm signal.
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
• Fixed current
4...20 mA NAMUR
0/4 mA value
Enter 4 mA value.
Signed floating-point number
0 kg/h
20 mA value
Enter 20 mA value.
Signed floating-point number
2.5 kg/h
Failure mode
Define output behavior in alarm condition.
• Min.
• Max.
• Last valid value
• Actual value
• Defined value
Max.
Failure current
Enter current output value in alarm
condition.
3.59 · 10
-3
to 22.5 · 10
-3
mA
22.5 mA