Electrical connection
Proline Cubemass C 100 HART
28
Hauser
7.2.4
Pin assignment, device plug
Supply voltage
1
2
4
3
5
A0016809
Pin
Assignment
1
L+
DC 24 V
2
Not assigned
3
Not assigned
4
L-
DC 24 V
5
Grounding/shielding
Coding
Plug/socket
A
Plug
Device plug for signal transmission (device side)
3
2
4
1
5
A0016810
Pin
Assignment
1
+
4-20 mA HART (active)
2
-
4-20 mA HART (active)
3
+
Pulse/frequency/switch output (passive)
4
-
Pulse/frequency/switch output (passive)
5
Grounding/shielding
Coding
Plug/socket
A
Socket
7.2.5
Preparing the measuring device
NOTICE
Insufficient sealing of the housing!
Operational reliability of the measuring device could be compromised.
‣
Use suitable cable glands corresponding to the degree of protection.
1. Remove dummy plug if present.
2. If the measuring device is supplied without cable glands:
Provide suitable cable gland for corresponding connecting cable.
3. If the measuring device is supplied with cable glands:
Observe requirements for connecting cables → 26.
7.3
Connecting the measuring device
NOTICE
Limitation of electrical safety due to incorrect connection!
‣
Have electrical connection work carried out by appropriately trained specialists only.
‣
Observe applicable federal/national installation codes and regulations.
‣
Comply with local workplace safety regulations.
‣
Always connect the protective ground cable before connecting additional cables.
‣
For use in potentially explosive atmospheres, observe the information in the device-
specific Ex documentation.
‣
The power unit must be tested to ensure it meets safety requirements (e.g. PELV,
SELV).