Modbus communication protocol
80
given value
Communication
EAO2
given value
1D05H Read-write
Range:0
~
4000
(
4000 represents
10.00V or 20.00mA
)
Communication DO
given value
1D06H Read-write
Range:0
~
4000
(
4000 represents
10.00V or 20.00mA
)
Communication EDO
given value
1D07H Read-write
Range:0
~
4000
(
4000 represents
10.00V or 20.00mA
)
The communication
output terminal given
value
1D08H
Read-write
BIT0:Y1
BIT1:Y2
BIT2:Y3
BIT3: Y4
BIT4: RLY1
BIT5: EY1
BIT6: EY2
BIT7: EY3
BIT8: EY4
BIT9: ERLY1
BIT10: ERLY2
Communication
virtual input terminal
given value
1D09H Read-write
BIT0:CX1
…
BIT7: CX8
Positive toque
limited frequency
1D0AH Read-write
Range:0
~
60000
(
60000 represents 600.00Hz
)
Negative toque
limited frequency
1D0BH Read-write
Range:0
~
60000
(
60000 represents 600.00Hz
)
PID feedback voltage
1D0CH
Read-write
Range:0
~
4000
(
4000 represents 10.00V
)
Reserved 1D0DH /
A.7 Communication error processing
Inverter receiving data packet detection error, it finds reading&writing parameter address or
parameter value invalid, so reply to the host with communication error response packet.
Communication error response packet (host command code+80H) as command code, with 1 byte
error code.
Format for communication error response packet as follows:
ADR 01H
CMD 83H/86H
Communication error code
01H~06H (for details, please check below table)
Low byte of CRC checksum
Obtain by calculating
High byte of CRC checksum
Obtain by calculating
Meaning for each communication error code value as follows:
Communication error code value
Communication error type
Priority
0x01
CRC checksum error
1
0x02 Command
code
illega
2
0x03
Register address visited illegal
3
0x04
Value to write register illegal
4
ENC