Function parameter schedule graph
53
F19.19 Frequency
droop
rate when instant
power off
0.00
~
99.99Hz/s 0.01Hz/s 10.00Hz/s
×
F19.20 Voltage
rebound
estimate time when
instant power off
0.00
~
10.00s 0.01s
0.10s
×
F19.21 Action
estimate
voltage when
instant power off
60
~
100% (Rated busbar voltage)
1%
80%
×
F19.22 Allowed
the
longest
off time when
instant power off
0.30
~
5.00s 0.01s
2.00s
×
F19.23 Terminal
external
device fault action
selection
0:Alarm,continuous run
1:Alarm,stop run as halt mode
2:Fault,free halt
1
2
×
F19.24 Power
on
terminal
protection selection
0:Invalid
1:Valid
1
0
×
F19.25 Provide
lost
detection value
0
~
100% 1%
0%
○
F19.26 Provide
lost
detection time
0.0
~
500.0s 0.1s
0.5s
○
F19.27 Feedback
lost
detection value
0
~
100% 1%
12%
○
F19.28 Feedback
lost
detection time
0.0
~
500.0s 0.1s
0.5s
○
F19.29 Deviation
magnitude
abnormal detection
value
0
~
100% 1%
50%
○
F19.30 Deviation
magnitude
abnormal detection
time
0.0
~
500.0s 0.1s
0.5s
○
F19.31 Protection
action
selection 1
Units digit: PID provide loss detection act
0:No detection
1:Alarm, Continue run
2:Alarm, Stop run as halt mode
3:Fault, Free halt
Tens digit: PID feedback loss detection act
0:No detection
1:Alarm, Continue run
2:Alarm, Stop run as halt mode
3:Fault, Free halt
Hundreds digit: PID error value abnormal detect
action
0:No detection
1:Alarm, Continue run
2:Alarm, Stop run as halt mode
3:Fault, Free halt
1 000
○
F19.32 Protection
action
selection 2
Units digit: communication abnormal action: include
communication time out and error
0:Alarm, Continue run
1:Alarm, Stop run as halt mode
2:Fault, Free halt
Tens digit: E
2
PROM abnormal action selection
0:Alarm, Continue run
1:Alarm, Stop run as halt mode
1 0200 ×