Troubleshooting
72
F26.06
Output current at previous failure
F26.15
Module temp. at previous 2 failure
F26.07
DC bus volt. at previous failure
F26.16
Input terminal state of previous 2
failure
F26.08
Module temp. at previous failure
F26.17
Running time of previous 2 failure
7.3 Failure reset
To resume normal running when failure takes place in the inverter, you can choose following
any kind of operation:
(1) After you set any terminal of X1~X8 to be inputted by external RESET, it will be reset
after connected to COM.
(2) When failure code is displayed
,
press key after confirmed that it can be restoration.
(3) Communication reset. Please refer to annex description.
(4) Cut off power supply.
7.4 Alarm reset
When an alarm occurs, must eliminate alarm source which cause alarm, otherwise the alarm
cannot be eliminated, also cannot be reset by reset button.
(1) Before reset you must find out reason of failure downright and eliminate
it,otherwise may cause permanent damage to the inverter.
(2) If can’t reset or failure takes place again after resetting, should look for reason and
continuous resetting will damage the inverter
(3) Reset should take place 5 minutes later after overload, overheat protection action.
(4) For the fault of E-14, the reset is invalid, the motor wiring should be checked after
power off, and restart the inverter.
(5) When there is a fault of E-16 after power on, do not directly run the inverter after
reset, and need to check whether the input,outwiring are reversed.
!