Function parameter schedule graph
51
0: Invalid
1: Valid
Thousands digit
:
in torque control mode,Low torque
given PWM blocking function
(Thousands digit is valid when F00.24=1)
0: Invalid
F18.17 cooling
fan
control
selection
Units digit: Fan control mode
0: Smart fan
1: Inverter is running all the time after power on
2: No running for fan, but it starts automatically when
the temperature is higher than 75 degree. Tens digit:
Speed regulation fan control mode.
0: Smart PWM Speed regulation
1: Running at highest speed.
1
00
○
F18.18 No speed vector
slip gain
50%
~
200% (When F00.24=1,this function is Valid)
1%
100%
○
F18.19 Low-order of total
power
consumption
0
~
9999 1kwh
0
○
F18.20 High-order
of
total
power
consumption
0
~
65535 (1represent 10000kwh)
10000
kwh
0
○
F18.21 Correction
factor
of
power consumption
calc ulation
50.0%
~
200.0% 0.1%
100.0%
○
F18.22 V/F
separate
control voltage
reference channel
0: Digital setting (Determined by 18.23)
1: AI1 analog setting
2: AI2 analog setting
3: Terminal UP / DOWN adjustment setting
4: Reserved
5: EAI1 analog Setting (Extended Valid)
6: EAI2 analog setting (Extended Valid)
7: High-speed pulse setting
(X8 terminals need to select the appropriate function)
8: Terminal pulse width setting
(X8 terminals need to select the appropriate function)
Note: The maximum value of 0 ~ 8 channels
correspond to the motor rated voltage.
1
1
○
F18.23 V/F separate
control voltage
digital reference
0.0%
~
100.0% 0.1%
0.0%
○
F18.24 Low
frequency
slip
gain
30
~
300% 1%
100%
○
F19
-
Protective Relevant Function Parameter Group
Function
code
Name
Set range
Min.
unit
Factory
default
Modifi
-cation
F19.00 Power off restart
waiting time
0.0
~
20.0s (0 means no start function)
0.1s
0.0s
×
F19.01 Fault
self-recovery
times
0
~
10 (0 means no automatic reset function)
1
0
×
F19.02 Fault
self-recovery
interval time
0.5
~
20.0s 0.1s
5.0s
×
F19.03 Motor
overload
protection action
selection
0: Alarm: continuous run
1: Alarm,stop run as halt mode
2: Fault,free halt
1
2
○