5 DXE-EXT-SET configuration module
5.3 Description and use
76
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
Mode 9
Machine control (2), ENA enable signal
The operating direction will be determined based
on the DIR (Low = FWD / High = REV) control
command. The frequency reference value is set via
the potentiometer (0 - +10 V).
An external fault message (EXT FLT) can be
connected to input DI3.
Note:
If there is a wire breakage at DI2 (DIR = REV), the
operating direction will be reversed automatically
(FWD)!
element
Behavior
Description
EXTFLT
DIR
ENA
f-REF
0 V
4
3
2
1
+10 V