9.9 DX-LN… mains chokes
The DE1 variable speed starter's rated input currents serve as the basis used
to determine which mains chokes should be used.
T
figure 92: main chokes DEX-LN…
→
If the DE1 variable speed starter is being run at its rated
operational current limit, the variable speed starter's maximum
possible output voltage (U
2
) will be reduced to about 96% of the
mains voltage (U
LN
) due to the mains choke at a u
k
value of
approximately 4%.
→
If using DE1-34… variable speed starters, the mains choke's u
k
value must not exceed 4%, as these devices feature a "lean DC
link."
→
Mains chokes reduce the magnitude of the current harmonics
up to about 30 % and increase the lifespan of variable speed
starters and upstream-connected switchgear.
Further information and technical data on the mains
chokes of the DX-LN… series is provided in Instruction
leaflet IL00906003Z.
a
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...