![Eaton PowerXL DE1 series Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/eaton/powerxl-de1-series/powerxl-de1-series_manual_525188060.webp)
3 Installation
3.3 Electrical Installation
56
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
Table 11: Connection examples for the digital inputs (mode 0)
connection terminals
Description
Default settings
The digital inputs (DI1 - DI3) and the frequency
reference (AI1) are driven with the in10 V
control voltage through potentiometer R1 (0 - 10 V).
External control voltage 24 V
The digital inputs (DI1 - DI3) are driven with an
external control voltage (+24 V).
The frequency reference is set with the in10 V
control voltage through potentiometer R1 (0 - 10 V).
External control voltage through PLC
The digital inputs (DI1 - DI3) are driven with an
external control voltage (+24 V).
The frequency reference is set with the external
0...+10 V value.
Note:
The signal common for the PLC's analog and digital
outputs is 0 V.
AI1
DI4
DI3
DI2
DI1
4
3
2
1
+10 V
X1
R1
+10 V
< 20 mA
0 V
+10...+24 V DC
FF1
REV
FWD
f-REF
AI1
DI4
DI3
DI2
DI1
4
3
2
1
+10 V
X1
R1
+10 V
< 20 mA
0 V
+24 V
+10...+24 V DC
FF1
REV
FWD
f-REF
f-REF
FF1
REV
FWD
AI1
DI4
DI3
DI2
DI1
4
3
2
1
+10 V
X1
+10 V
< 20 mA
0 V
U
+24 V
+10...+24 V DC
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...