2 Engineering
2.4 EMC measures
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
29
figure 17: cable routing
figure 18: Separate routing
a
Power cable: mains voltage, motor connection
b
Control and signal lines, fieldbus connections
→
Do not route the control and signal cables
②
in the same
conduit as the power cables
①
.
Analog signal cables (measured values, setpoints, and
correction values) must be routed inside screened conduit.
≧
300 mm
(≧ 11.81“)
②
①
a
b
a
b