9 Accessory devices
9.2 DX-COM-STICK communications stick
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
147
The arrow buttons on the DX-COM-STICK communication stick can be used
to control the direction in which parameters will be transferred:
The parameters will be copied from the DX-COM-STICK
communications stick to the connected device (
⑥
).
The parameters will be copied from the connected device to the
DX-COM-STICK communication stick
(
⑤
)
.
In order to be able to establish a connection to a computer (with the
drivesConnect parameter configuration program), the DX-COM-STICK
Bluetooth communication stick needs to be activated with the "Add a
Bluetooth Device" Windows function and code 0000.
When using DX-COM-STICK, the 3 LEDs on the front of the variable speed
starter DE1 give additional information about the status.
Table 42: DX-COM-STICK
→
For more information on the DX-COM-STICK Bluetooth
communication stick, please refer to manual MN040003EN,
"drivesConnect · Parameter Configuration Program for
PowerXL™ Variable Speed Starters" and to Instruction leaflet
IL04012021Z..
→
When transferring parameters between devices belonging to
the DE1 series, it is important to note that it will only be possible
to copy rating-related parameters (e.g., current values) to
devices belonging to the same rating category.
LED Status
LED1
fast flash for 2 s (4 Hz), green
Read/Write parameter pass
LED FLT
off
LED FLT Code
off
LED1
fast flash for 2 s (4 Hz), green
Read/Write parameter failed
LED FLT
fast flash for 2 s (4 Hz), red
LED FLT Code
fast flash for 2 s (4 Hz), red
LED1
fast flash for 2 s (4 Hz), green
Read/write disabled e.g because
DX-COM-STICK is locked, DE1 is running
or DE1 type mismatch
LED FLT
fast flash for 2 s (4 Hz), yellow
LED FLT Code
fast flash for 2 s (4 Hz), yellow
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...