6 Parameters
6.5 Parameter description
88
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
6.5.2 Motor Data
figure 63: Motor parameters from ratings plate
When selecting the rating data, take the dependency of the circuit types on
the mains voltage into account:
•
230 V in P-07
→
Delta circuit
→
P-08 = 3.2 A
•
400 V in P-07
→
Star connection
→
P-08 = 1.9 A
figure 64: Circuits (delta, star)
→
When the DE1 variable speed starter is used with its default
settings, the motor data (P-07, P-08, P-09) will match the
starter's rated operational data. This means that the default
motor data will depend on the DE1 model being used.
→
Parameter P-10 will be set to 0 by default, i.e., to the V/f
frequency control mode. If the motor speed is set here, slip
compensation will be automatically activated and all frequency-
based parameters will be shown in rpm, Table 23, page 93.
1410 min
230/400 V
3.2/1.9 A
50 Hz
-1
0.75 kW
cos ϕ 0.79
P-07
P-08
P-10
P-09
U1
V1
W1
W2
U2
V2
U1
V1
W1
W2
U2
V2
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...