5 DXE-EXT-SET configuration module
5.1 DXE-EXT-SET designation
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
69
5 DXE-EXT-SET configuration module
figure 52: DXE-EXT-SET configuration module
The DXE-EXT-SET configuration module can be used to easily change the
default settings for a DE1 variable speed starter without having to use a
keypad or a computer. DXE-EXT-SET works like a mechanical parameter
storage unit. For example, it can be used to transfer (copy) the values set
with it (STATUS LED lit up with a green light) to other DE1 variable speed
starters with the same output rating (SET pushbutton).
5.1 DXE-EXT-SET designation
figure 53: DXE-EXT-SET designation
a
Status LED
b
Mounting clips for DE1 variable speed starters
c
50/60 Hz selector switch – used to automatically adjust the default settings as required for the mains
frequency being used
d
SET pushbutton – used to transfer the modified settings to the DE1 variable speed starter
e
I Motor potentiometer – can be used to adjust the motor protection setting (I
2
t value)
f
Mode selector switch – used to configure the control terminals' functions
g
Ramp selector switch – used to change the ramp times (acceleration and deceleration)
h
Fixed Freq. potentiometer – used to adjust fixed frequency FF1 within the range defined by the
minimum and maximum limits
i
Mode – overview of control terminal configurations
→
The DXE-EXT-SET configuration module is an optional accessory
and is not included as standard with the DE1 variable speed
starter.
STATUS
SET
DXE-EXT-SET
50Hz
60Hz
min
max
25%
0
9
8
7
6
5
4
180s
3
2
1
I Motor
Mode
Fixed Freq.
Ramp
100%
1s
0.1s
3s
5s
10s
15s
30s
60s
120s
STATUS
SET
DXE-EXT-SET
50Hz
60Hz
min
max
25%
0
9
8
7
6
5
4
180s
3
2
1
I Motor
Mode
Fixed Freq.
Ramp
100%
1s
0.1s
3s
5s
10s
15s
30s
60s
120s
①
⑨
③
①
②
④
⑤
⑥
⑦
⑧
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...